Danfoss AVD (003H6660) — self-acting pressure reduction controller, PN 25, DN 40, for district heating and cooling systems. The AVD is a self-acting pressure reduction controller for district-heating water. It is normally open and closes on rising downstream pressure, holding the reduced (outlet) pressure constant at the setpoint. It has a control valve, an actuator with one control diaphragm and a spring for the pressure setting. Reduced-pressure setting range 1–5 bar adjustable; Kvs 20 m³/h. Maximum differential-pressure range 16 bar; media temperature 2–150 °C; cavitation factor z ≥ 0.6; seat leakage 0.05 % Kvs (IEC 60534). Valve body Ductile iron EN-GJS-400-18-LT (GGG 40.3); valve cone Dezincing free brass CuZn36Pb2As; seat Stainless steel, mat. 1.4571; control diaphragm EPDM. Connection Flange, PN 25. Mounting version Flow. Permissible media: District heating/cooling circulation water (Glycolic water up to 30%). OEM P/N 003H6660. Technical data quoted verbatim from store.danfoss.com (code 003H6660) and the Danfoss AVD / AVD-S (PN 25) pressure reduction controller data sheet. 1.4571; control diaphragm EPDM; Pressure rating: PN 25 (max. differential-pressure range 16 bar); Temperature range: 2 to 150 °C (district heating/cooling water); HS code: 8481.80. Used in commercial refrigeration, provision-room cooling and reefer plant rooms across HFC, HFO and CO2 (R744) refrigerants.
| Code number | 003H6660 |
| Type | AVD |
| Product group | Pressure and flow controllers (pressure reduction controller) |
| Function | Self-acting pressure reduction controller (closes on rising downstream pressure) |
| Valve size | DN 40 |
| Pressure class | PN 25 |
| Connection | Flange, PN 25 |
| Kvs value | 20 m³/h |
| Pressure setting range | 1 - 5 bar (reduced/outlet, adjustable) |
| Max. differential pressure range | 16 bar |
| Media temperature | 2 - 150 °C |
| Cavitation factor z | ≥ 0.6 |
| Seat leakage rate | 0.05 % Kvs (IEC 60534) |
| Mounting version | Flow |
| Stem position | Normally open |
| Permissible media | District heating/cooling circulation water (Glycolic water up to 30%) |
| Valve body material | Ductile iron EN-GJS-400-18-LT (GGG 40.3) |
| Valve cone material | Dezincing free brass CuZn36Pb2As |
| Valve seat material | Stainless steel, mat. No. 1.4571 |
| Actuator diaphragm | EPDM |
| EU RoHS compliance | Yes with exemptions (6(c)) |
| REACH Candidate List substance | Lead (CAS no. 7439-92-1) |
| China RoHS | Out of scope |
| Net weight | 12.542 kg |
| Gross weight | 12.542 kg |
| EAN | 5702421541814 |
| Material | Valve body Ductile iron EN-GJS-400-18-LT (GGG 40.3); valve cone Dezincing free brass CuZn36Pb2As; valve seat Stainless steel, mat. No. 1.4571; control diaphragm EPDM |
| Pressure rating | PN 25 (max. differential-pressure range 16 bar) |
| Temperature range | 2 to 150 °C (district heating/cooling water) |
| MOQ | 1 |
Danfoss AVD for DN 40 district-heating/cooling circuits at PN 25. Set the reduced-pressure setpoint within 1–5 bar. Confirm the connection (Flange, PN 25) and pressure class (PN 25) match the pipework; order the matching counter-flange and impulse tube separately. Maximum differential-pressure range 16 bar, media temperature up to 150 °C.