Danfoss ASV-M DN 32 Internal thread shut-off / partner valve (003L7694)

Danfoss · HVAC & Refrigeration · Balancing Valves · Denmark · danfoss.com
Part Number
003L7694  ·  HS 8481.80
Danfoss ASV-M DN 32 Internal thread shut-off / partner valve (003L7694)

Danfoss ASV-M — shut-off partner valve, OEM order code 003L7694. Shut-off partner valve for the supply pipe of a riser controlled by a Danfoss ASV-P or ASV-PV differential-pressure controller (the controller impulse tube connects here). It provides positive shut-off of the branch/riser without a presetting scale, so the balanced circuit can be isolated for service. Used where flow measurement/presetting is handled elsewhere in the riser. (ASV-M DN 32, internal thread, shut-off valve.) Nominal size DN 32, Kvs 6.3 m³/h, PN 16, Internal thread connection, Brass body, media temperature -20 °C to 120 °C. Net weight 1.075 Kilogram. Genuine Danfoss part; technical data quoted verbatim from store.danfoss.com (code 003L7694). OEM P/N 003L7694, EAN 5702421528099.

Technical Specifications

BrandDanfoss
Part number003L7694
TypeASV-M
Product groupAutomatic balancing
Functionshut-off partner valve
Store descriptionASV-M DN 32, internal thread, shut-off valve
Nominal sizeDN 32
Kvs value6.3 m³/h
Connection typeInternal thread
Pressure classPN 16
Max. differential pressure over the valve150 KPa
Mounting positionSupply pipe
Setting scaleNo
Flow limitationYes
Shut-off functionYes
Drain functionNo
Valve body materialBrass
Media temperature-20 °C to 120 °C
REACH candidate-list substancesLead (CAS no. 7439-92-1)
Net weight1.075 Kilogram
Gross weight1.324 Kilogram
EAN5702421528099
HS code8481.80 (taps, cocks, valves for pipes, tanks, vats or the like)

Properties

MaterialValve body Brass
Pressure ratingPN 16
Temperature range-20 °C to 120 °C (media)
MOQ1

Compatibility

Shut-off partner valve fitted on the supply of a riser controlled by a Danfoss ASV-P/ASV-PV differential-pressure controller; the controller impulse tube connects here. Match the nominal size (DN 32) and connection (Internal thread) to the controller and pipework. Provides positive shut-off; use ASV-I instead where presetting/measurement is required at this point.

Approvals

Attached Documents