Danfoss APT automatic balancing valve, DN 25, OEM order code 003Z5743. The APT is a self-acting differential-pressure control valve for hydronic distribution: it holds the differential pressure across a branch or terminal within its 20 KPa-60 KPa kPa adjustable range (factory setting 30 KPa), using an integral impulse tube (1.5 m) to sense the pressure across the served circuit. This keeps thermostatic/terminal control valves authoritative and the circuit balanced across the full load range without manual re-commissioning. internal thread connection, brass body, PN 16, Kvs 4 m³/h m³/h, media 0 °C … 120 °C °C, max. differential pressure over the valve 250 KPa. Mounting: return pipe. Genuine Danfoss part; data quoted verbatim from store.danfoss.com (code 003Z5743). OEM P/N 003Z5743, EAN 5710104094694. Used in commercial refrigeration, provision-room cooling and reefer plant rooms across HFC, HFO and CO2 (R744) refrigerants.
| Brand | Danfoss |
| Part number | 003Z5743 |
| Gross weight | 1.463 Kilogram |
| Net weight | 1.093 Kilogram |
| Type | APT |
| Product group | Automatic balancing |
| Connection types | Internal thread |
| Description | APT DN 25, 20-60 kPa, Internal thread, without insulation, automatic balancing valve |
| Differential pressure over the valve [kPa] [Max] | 250 KPa |
| Differential pressure setting [kPa] [Max] | 60 KPa |
| Differential pressure setting [kPa] [Min] | 20 KPa |
| Factory setting [kPa] | 30 KPa |
| Impulse tube length [m] | 1.5 m |
| Insulation | Without insulation |
| Kvs values [m³/h] | 4 m³/h |
| Media temperature [°C] [Max] | 120 °C |
| Media temperature [°C] [Min] | 0 °C |
| Mounting position | Return pipe |
| Pressure class | PN 16 |
| Shut-off function | Yes |
| Valve body material | Brass |
| Valve size | DN 25 |
| EAN | 5710104094694 |
| HS code | 8481.80 (taps, cocks, valves for pipes, tanks, vats or the like) |
| Material | Valve body brass |
| Pressure rating | PN 16 |
| Temperature range | 0 °C … 120 °C |
| MOQ | 1 |
Self-acting differential-pressure automatic balancing valve for DN 25 internal thread circuits. Fit in the return pipe; set the target differential (20 KPa-60 KPa kPa) at commissioning. Kvs 4 m³/h m³/h. Confirm DN 25, connection (Internal thread) and the 20 KPa-60 KPa kPa range against the branch design before ordering.