Danfoss AFPQ 2 PN 40 self-acting differential-pressure & flow controller actuator — return-mounted, setting 0.2–1 bar, 320 cm² diaphragm, valve DN 150–250 (003G5715)

Danfoss · HVAC & Refrigeration · Balancing Valves · Denmark · danfoss.com
Part Number
003G5715  ·  HS 8481.90
Danfoss AFPQ 2 PN 40 self-acting differential-pressure & flow controller actuator — return-mounted, setting 0.2–1 bar, 320 cm² diaphragm, valve DN 150–250 (003G5715)

Danfoss AFPQ 2 PN 40 — a self-acting combined differential-pressure and flow controller. A single rolling-diaphragm actuator both holds the differential pressure across the controlled section constant and limits the maximum flow to a preset value, without external power. This return-mounted (AFPQ 2) variant senses across the consumer and throttles the matching globe valve body to maintain the set differential pressure while capping flow at the adjusted flow-restrictor setting. The actuator carries the diaphragm and setting spring only; it combines with a Danfoss VFG 2 / VFGS 2 / VFU 2 globe valve body (ordered separately) to form a complete self-acting controller for district heating and district cooling circuits. Actuator diaphragm area 320 cm²; differential-pressure setting 0.2–1 bar; suits valve bodies DN 150–250. Media temperature 2 °C to 150 °C; maximum operating pressure 40 bar. Actuator housing Steel, mat. 1.0345, zinc plated; diaphragm EPDM (Rolling, fibre enforced). Medium: district heating/cooling circulation water (glycolic water up to 30%). OEM designation "AFPQ 2, PN 40, 0.2 bar - 1 bar, 320 cm²". OEM P/N 003G5715. Technical data quoted verbatim from store.danfoss.com (code 003G5715). 1.0345, zinc plated; diaphragm EPDM (Rolling, fibre enforced); Standard size: AFPQ 2; Pressure rating: PN 40; Temperature range: 2 °C to 150 °C; HS code: 8481.90. Used in commercial refrigeration, provision-room cooling and reefer plant rooms across HFC, HFO and CO2 (R744) refrigerants. No.

Technical Specifications

Code number003G5715
TypeAFPQ 2
Product groupActuators - Pressure Flow
Gross weight46.6 Gram
Net weight38.1 Gram
Volume191.52 Liter
Actuator diaphragm materialEPDM (Rolling, fibre enforced)
Actuator size [cm²]320 cm²
Body materialSteel, mat. No. 1.0345, zinc plated
China RoHS complianceOut of scope
Contains batteriesNo
Diameter [mm] [Max]250 mm
Diameter [mm] [Min]150 mm
Differential pressure setting [bar] [Max]1 bar
Differential pressure setting [bar] [Min]0.2 bar
EU RoHS complianceOut of scope
Flow controlNo
Flow limitationNo
Flow restrictor diff.pressure - dpb [bar]0.5 bar
FunctionDiff. press. and flow controller
Media pH [Max]10
Media pH [Min]7
Media temperature [°C] [Max]150 °C
Media temperature [°C] [Min]2 °C
Medium alternativeGlycolic water up to 30%
Mounting versionReturn
Operating pressure [bar] [Max]40 bar
Permissible mediaDistrict heating/cooling circulation water
Pressure classPN 40
Pressure controllerDifferential pressure controller
Pressure nominal [bar]40 bar
Pressure setting range [bar] [Max]1 bar
Pressure setting range [bar] [Min]0.2 bar
REACH Candidate List substancesLead (CAS no. 7439-92-1)
Setting TypeAdjustable
EAN5715162375013
HS code8481.90
Nominal diameterDN150

Properties

MaterialActuator housing Steel, mat. No. 1.0345, zinc plated; diaphragm EPDM (Rolling, fibre enforced)
Pressure ratingPN 40
Temperature range2 °C to 150 °C
Standard sizeAFPQ 2
MOQ1

Compatibility

AFPQ 2 is the self-acting combined differential-pressure and flow controller actuator of the Danfoss AF range; it combines with a Danfoss VFG 2 / VFGS 2 / VFU 2 globe valve body to build a complete controller. Select by pressure class (PN 40), required differential-pressure setting range (0.2–1 bar), actuator size (320 cm²), mounting side (return) and the valve-body size range (DN 150–250). For flow-line mounting use AFPQ 24; for differential-pressure control only use AFP; for flow limitation only use AFQ; for differential-pressure relief use AFPA; for pressure reduction use AFD. Confirm actuator size, setting range and matching valve body against the AF-range data sheet before ordering.

Attached Documents