cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-08
sales@cballast.com
cballast.com

Danfoss AFPA 2 PN 16 self-acting differential-pressure-relief actuator — setting 1.5–6 bar, 80 cm² diaphragm, valve DN 65–125 (003G5689)

Danfoss · HVAC & Refrigeration · Balancing Valves · Denmark · danfoss.com
Part Number
003G5689  ·  HS 8481.90
Danfoss AFPA 2 PN 16 self-acting differential-pressure-relief actuator — setting 1.5–6 bar, 80 cm² diaphragm, valve DN 65–125 (003G5689)

Danfoss AFPA 2 PN 16 — a self-acting differential-pressure-relief controller (surplus differential-pressure / overflow controller). It opens the matching globe valve body via its rolling-diaphragm actuator when the differential pressure across the controlled section exceeds the spring setting, discharging surplus flow through a bypass to hold the differential pressure at the set maximum. The actuator carries the diaphragm and setting spring only; it combines with a Danfoss VFG 2 / VFGS 2 / VFU 2 globe valve body (ordered separately) to form a complete self-acting controller for district heating and district cooling circuits. Actuator diaphragm area 80 cm²; setting 1.5–6 bar; suits valve bodies DN 65–125. Media temperature 2 °C to 150 °C; maximum operating pressure 16 bar. Actuator housing Steel, mat. 1.0345, zinc plated; diaphragm EPDM (Rolling, fibre enforced). Medium: district heating/cooling circulation water (glycolic water up to 30%). OEM designation "AFPA 2, PN 16, 1.5 bar - 6 bar, 80 cm²". OEM P/N 003G5689. Technical data quoted verbatim from store.danfoss.com (code 003G5689). 1.0345, zinc plated; diaphragm EPDM (Rolling, fibre enforced); Standard size: AFPA 2; Pressure rating: PN 16; Temperature range: 2 °C to 150 °C; HS code: 8481.90. Used in commercial refrigeration, provision-room cooling and reefer plant rooms across HFC, HFO and CO2 (R744) refrigerants. No.

Technical Specifications

Code number003G5689
TypeAFPA 2
Product groupActuators - Pressure Flow
Gross weight12.371 Kilogram
Net weight10 Kilogram
Volume52.746 Liter
Actuator diaphragm materialEPDM (Rolling, fibre enforced)
Actuator size [cm²]80 cm²
ApplicationDistrict heating and cooling
Body materialSteel, mat. No. 1.0345, zinc plated
China RoHS complianceOut of scope
Contains batteriesNo
DescriptionDifferential pressure relief actuator
Diameter [mm] [Max]125 mm
Diameter [mm] [Min]65 mm
Differential pressure setting [bar] [Max]6 bar
Differential pressure setting [bar] [Min]1.5 bar
EU RoHS complianceOut of scope
Flow controlNo
Flow limitationNo
FunctionDiff. press. relief controller
Media pH [Max]10
Media pH [Min]7
Media temperature [°C] [Max]150 °C
Media temperature [°C] [Min]2 °C
Medium alternativeGlycolic water up to 30%
Mounting versionBypass
Operating pressure [bar] [Max]16 bar
Permissible mediaDistrict heating/cooling circulation water
Pressure classPN 16
Pressure controllerDifferential pressure relief controller
Pressure nominal [bar]16 bar
REACH Candidate List substancesLead (CAS no. 7439-92-1)
Setting TypeAdjustable
EAN5715162292587
HS code8481.90
Nominal diameterDN65

Properties

MaterialActuator housing Steel, mat. No. 1.0345, zinc plated; diaphragm EPDM (Rolling, fibre enforced)
Pressure ratingPN 16
Temperature range2 °C to 150 °C
Standard sizeAFPA 2
MOQ1

Compatibility

AFPA 2 is the self-acting actuator of the Danfoss AF range; it combines with a Danfoss VFG 2 / VFGS 2 / VFU 2 globe valve body to build a complete controller. Select by pressure class (PN 16), required setting range (1.5–6 bar), actuator size (80 cm²) and the valve-body size range (DN 65–125). For plain pressure relief use AFA; for differential-pressure control (constant, not relief) use AFP; for pressure reduction use AFD. AFPA mounts in a bypass line. Confirm actuator size, setting range and matching valve body against the AF-range data sheet before ordering.

Attached Documents