cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-08
sales@cballast.com
cballast.com

Danfoss AFA 2 PN 16 self-acting pressure-relief actuator — setting 1–3 bar, 160 cm² diaphragm, valve DN 65–250 (003G5662)

Danfoss · HVAC & Refrigeration · Balancing Valves · Denmark · danfoss.com
Part Number
003G5662  ·  HS 8481.90
Danfoss AFA 2 PN 16 self-acting pressure-relief actuator — setting 1–3 bar, 160 cm² diaphragm, valve DN 65–250 (003G5662)

Danfoss AFA 2 PN 16 — a self-acting pressure-relief controller (surplus-pressure / overflow controller). It opens the matching globe valve body via its rolling-diaphragm actuator when the controlled pressure rises above the spring setting, discharging surplus flow to hold the upstream pressure at the set maximum. The actuator carries the diaphragm and setting spring only; it combines with a Danfoss VFG 2 / VFGS 2 / VFU 2 globe valve body (ordered separately) to form a complete self-acting controller for district heating and district cooling circuits. Actuator diaphragm area 160 cm²; setting 1–3 bar; suits valve bodies DN 65–250. Media temperature 2 °C to 150 °C; maximum operating pressure 16 bar. Actuator housing Steel, mat. 1.0345, zinc plated; diaphragm EPDM (Rolling, fibre enforced). Medium: district heating/cooling circulation water (glycolic water up to 30%). OEM designation "AFA 2, PN 16, 1 bar - 3 bar, 160 cm²". OEM P/N 003G5662. Technical data quoted verbatim from store.danfoss.com (code 003G5662). 1.0345, zinc plated; diaphragm EPDM (Rolling, fibre enforced); Standard size: AFA 2; Pressure rating: PN 16; Temperature range: 2 °C to 150 °C; HS code: 8481.90. Used in commercial refrigeration, provision-room cooling and reefer plant rooms across HFC, HFO and CO2 (R744) refrigerants. No.

Technical Specifications

Code number003G5662
TypeAFA 2
Product groupActuators - Pressure Flow
Gross weight14.7 Kilogram
Net weight12.5 Kilogram
Volume49.619 Liter
Actuator diaphragm materialEPDM (Rolling, fibre enforced)
Actuator size [cm²]160 cm²
Body materialSteel, mat. No. 1.0345, zinc plated
China RoHS complianceOut of scope
Contains batteriesNo
DescriptionPressure relief actuator
Diameter [mm] [Max]250 mm
Diameter [mm] [Min]65 mm
Differential pressure setting [bar] [Max]3 bar
Differential pressure setting [bar] [Min]1 bar
EU RoHS complianceOut of scope
Flow controlNo
Flow limitationNo
FunctionPress. relief controller
Media pH [Max]10
Media pH [Min]7
Media temperature [°C] [Max]150 °C
Media temperature [°C] [Min]2 °C
Medium alternativeGlycolic water up to 30%
Mounting versionBypass
Operating pressure [bar] [Max]16 bar
Permissible mediaDistrict heating/cooling circulation water
Pressure classPN 16
Pressure controllerPressure relief controller
Pressure nominal [bar]16 bar
Pressure setting range [bar] [Max]3 bar
Pressure setting range [bar] [Min]1 bar
Setting TypeAdjustable
EAN5710104096179
HS code8481.90
Nominal diameterDN65

Properties

MaterialActuator housing Steel, mat. No. 1.0345, zinc plated; diaphragm EPDM (Rolling, fibre enforced)
Pressure ratingPN 16
Temperature range2 °C to 150 °C
Standard sizeAFA 2
MOQ1

Compatibility

AFA 2 is the self-acting actuator of the Danfoss AF range; it combines with a Danfoss VFG 2 / VFGS 2 / VFU 2 globe valve body to build a complete controller. Select by pressure class (PN 16), required setting range (1–3 bar), actuator size (160 cm²) and the valve-body size range (DN 65–250). For differential-pressure relief use AFPA; for pressure reduction use AFD; for differential-pressure control use AFP; for flow limitation use AFQ. AFA mounts in a bypass line. Confirm actuator size, setting range and matching valve body against the AF-range data sheet before ordering.

Attached Documents