Danfoss AKS 32 pressure transmitter for refrigeration and air-conditioning. Measuring range 0 to 34.5 bar (0 to 500 psi), ratiometric voltage output 1-5 V, digitally compensated ceramic/silicon sensor with AISI 316L stainless steel wetted parts. Pressure connection 1/8-27 NPT (male); electrical connection 5 m screened cable. Sealed-gauge reference; accuracy +/-0.3% typical. Approvals: ATEX Ex ec IIA T4 Gc, CE, UL Recognized (C UL US), GOST. EAN 5702422112112.
| Type | AKS 32 |
| Range | 0 to 34.5 bar (0 to 500 psi) |
| Output | 1-5 V (ratiometric) |
| Supply | 9-32 V DC |
| Wetted parts | AISI 316L stainless steel |
| Pressure connection | 1/8-27 NPT (male) |
| Electrical connection | Screened cable, 5 m |
| Reference | Sealed gauge |
| Enclosure | IP67 |
| Media temp | -40 to 85°C |
| Approvals | ATEX Ex ec IIA T4 Gc, CE, UL Recognized (C UL US), GOST |
| EAN | 5702422112112 |
| Part number | 060G2033 |
| Net weight | 0.363 Kilogram |
| Product group | Sensors |
| + output | Green |
| + supply | Red |
| - common | White |
| Accuracy, max. [±FS%] | 0.8 % |
| Accuracy, typical [±FS%] | 0.3 % |
| Adj. zero point and span | No |
| Ambient temperature range [°C] [max] | 85 °C |
| Ambient temperature range [°C] [min] | -40 °C |
| Ambient temperature range [°F] [max] | 185 °F |
| Ambient temperature range [°F] [min] | -40 °F |
| Approval | ATEX |
| Approval comments | ATEX Ex ec IIA T4 Gc |
| Approval standard | 6967179 |
| Cable length [in] | 196 in |
| Cable length [m] | 5 m |
| CE mark | Yes |
| China RoHS compliance | Out of scope |
| Compensated temp. range [°C] [max] | 80 °C |
| Compensated temp. range [°C] [min] | 0 °C |
| Compensated temp. range [°F] [max] | 176 °F |
| Compensated temp. range [°F] [min] | 32 °F |
| EEE category | 5 small equipment (any external dimension < 50 cm) |
| Electrical conn. comments | Screened |
| Enclosure rating IP | IP67 |
| EU RoHS compliance | Yes with exemptions |
| EU RoHS exemption clause | 6(c) |
| Flush diaphragm | No |
| High Clipping Level | 6.75 |
| In scope of WEEE | Yes |
| International Article Number | 5702422112112 |
| Intrinsically safe | No |
| Low Clipping level | 0.1 |
| Medium temperature range [°C] [max] | 85 °C |
| Medium temperature range [°C] [min] | -40 °C |
| Medium temperature range [°F] [max] | 185 °F |
| Medium temperature range [°F] [min] | -40 °F |
| Non-linearity BFSL [±FS%] | 0.2 % |
| Output signal | Voltage |
| Output signal [V] [max] | 6 V |
| Output signal [V] [min] | 1 V |
| Overload pressure max. [psi] | 800 psi |
| Pressure connection size | 1/8-27 |
| Pressure connection standard | ANSI/ASME B1.20.1 |
| Pressure connection type | NPT |
| Pressure Male/Female | Male |
| Pressure range [bar] [max] | 34.5 bar |
| Pressure range [bar] [min] | 0 bar |
| Pressure range [psi] [max] | 500 psi |
| Pressure range [psi] [min] | 0 psi |
| Pressure reference | Sealed gauge |
| Pulse-snubber | No |
| REACH Candidate List substances | Lead (CAS no. 7439-92-1) |
| Response time max. [ms] | 4 ms |
| Specification key | AKS 32-6634-D1AC02-0 |
| Supply voltage [V] DC [max] | 32 V |
| Supply voltage [V] DC [min] | 9 V |
| UL mark | Yes |
| Material | AISI 316L stainless steel wetted parts |
| Pressure rating | 0 to 34.5 bar |
| Temperature range | -40°C to +85°C (medium/ambient) |
| IP rating | IP67 |
| Thread standard | ANSI/ASME B1.20.1 |
| MOQ | 1 |
Cable-out IP67 variant with 1/8-27 NPT and 5 m screened cable; 0-500 psi gauge range.