Danfoss WVH 3 in Valve Body for WVS / WVTS Water Regulating Valve

Danfoss · HVAC & Refrigeration · Water Regulating Valves · Denmark · danfoss.com
Part Number
016D5080  ·  HS 8481.90
Danfoss WVH 3 in Valve Body for WVS / WVTS Water Regulating Valve

Danfoss WVH 3 in cast-iron valve body, OEM P/N 016D5080, for the pilot-operated WVS/WVTS 80 water regulating valve. The WVH body is the throttling main valve of the Danfoss modular water-valve system: a WVS pressure pilot (opens on rising pressure) or a WVTS thermostatic pilot (opens on rising temperature) mounts on top to control condenser cooling-water flow. Orifice 80 mm; Kv 80 m³/h; port connection Weld flange. Differential pressure range 0.3 – 4 bar; max working pressure 10 bar (145 psig); media temperature -25 °C to 90 °C; neutral media. Cast iron body. Supplied as single pack including valve body, flange bolts, flange gaskets and pilot-valve screws. Order the matching WVS or WVTS pilot separately.

Technical Specifications

BrandDanfoss
Part number016D5080
TypeWVH valve body for WVS / WVTS water regulating valve
CategoryHVAC & Refrigeration — Water Regulating Valves
Nominal sizeWVS/WVTS 80 (3 in)
Orifice size80 mm
Port connectionWeld flange
Kv80 m³/h
Differential pressure range0.3 – 4 bar
Max working pressure10 bar (145 psig)
Test pressure16 bar
Media temperature range-25 °C to 90 °C (-13 °F to 194 °F)
Body materialCast iron
MediaNeutral media (fresh water, neutral brine)
Parts includedValve body, flange bolts, flange gaskets, screws for pilot valve
PackingSingle pack
EAN5702422002710
ApprovalsEAC, PED, EU RoHS, China RoHS, LLC CDC TYSK
Net weight22.102 Kilogram
Product groupWater regulating valves
ApprovalEAC
China RoHS complianceOut of scope
Connection size [in]3 in
Connection typeWeld flange
Differential pressure [bar] [max]4 bar
Differential pressure [bar] [min]0.3 bar
Differential pressure [psi] [max]58 psi
Differential pressure [psi] [min]4.3 psi
EU RoHS complianceOut of scope
Kv value [m³/h]80 m³/h
Max. test pressure [bar] Pe16 bar
Max. test pressure [psig]232 psig
Max. Working Pressure [bar]10 bar
Max. Working Pressure [psig]145 psig
Medium temperature range [°C] [max]90 °C
Medium temperature range [°C] [min]-25 °C
Medium temperature range [°F] [max]194 °F
Medium temperature range [°F] [min]-13 °F
Orifice size [mm]80 mm
Orifice size fraction [in]3 in
REACH Candidate List substancesLead (CAS no. 7439-92-1)
Used for productWVS 80

Properties

MaterialCast iron
Pressure rating10 bar (145 psig) max working pressure; 16 bar test pressure
Temperature range-25 °C to 90 °C
Standard sizeWVS/WVTS 80
Thread standardWeld flange
MOQ1

Compatibility

Fit in the condenser cooling-water line with the flow arrow in the direction of flow. Mount a WVS pressure pilot or a WVTS thermostatic pilot on the body per the application. Body common to WVS/WVTS 80. Confirm code, connection and pilot type before ordering.