Danfoss WVTS thermostatic pilot, OEM P/N 016D1007, for the pilot-operated WVS/WVTS water regulating valve. The pilot mounts on the WVH valve body and opens the main valve on rising sensor temperature, modulating cooling-water flow to hold a temperature set point (self-acting, no external power). Temperature setting range 50 °C – 90 °C; charged sensor with 5000 mm capillary tube; maximum permissible sensor temperature 125 °C. Fits all valve sizes WVTS 32, 40, 50, 65, 80 and 100. Supplied as a control element with spring housing. Order the matching WVH valve body separately.
| Brand | Danfoss |
| Part number | 016D1007 |
| Type | WVTS thermostatic pilot for water regulating valve |
| Category | HVAC & Refrigeration — Water Regulating Valves |
| Function | opens the main valve on rising temperature (self-acting thermostatic pilot) |
| Temperature setting range | 50 °C – 90 °C |
| Capillary tube length | 5000 mm (5 m) |
| Max. sensor temperature | 125 °C |
| Fits valve sizes | WVTS 32, 40, 50, 65, 80, 100 |
| Parts included | Control element, spring housing |
| Media | Water |
| Packing | Multi pack (8 pc) |
| EAN | 5702422024736 |
| Approvals | EAC, PED (WVS / WVTS valve system) |
| Note | Sensor charge contains lead (REACH Candidate List, CAS 7439-92-1) |
| Net weight | 0.953 Kilogram |
| Product group | Water regulating valves |
| Cap. tube length fraction [in] | 196 27/32 in |
| Capillary tube length [mm] | 5000 mm |
| China RoHS compliance | Out of scope |
| EU RoHS compliance | Out of scope |
| Max. sensor temperature [°C] | 125 °C |
| Max. sensor temperature [°F] | 257 °F |
| REACH Candidate List substances | Lead (CAS no. 7439-92-1) |
| Temperature range [°C] [max] | 90 °C |
| Temperature range [°C] [min] | 50 °C |
| Temperature range [°F] [max] | 194 °F |
| Temperature range [°F] [min] | 122 °F |
| Used for product | WVTS 100 |
| Material | Charged temperature sensor with capillary; control element and spring housing |
| Temperature range | 50 °C – 90 °C setting range |
| Standard size | WVTS 32 – 100 (all sizes) |
| MOQ | 1 |
Mount on the matching WVH valve body (016D5032–5100). Place the sensor in the medium to be controlled. Opens on rising temperature — use for e.g. condenser water temperature control. Confirm setting range 50 °C – 90 °C and capillary length 5 m before ordering.