cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Danfoss GBC 12S Shut-off Ball Valve 1/2 in Solder ODF 009G7022

Danfoss · HVAC & Refrigeration · Ball Valves · Denmark · danfoss.com
Part Number
009G7022  ·  HS 8481.80
Danfoss GBC 12S Shut-off Ball Valve 1/2 in Solder ODF 009G7022

Danfoss GBC 12s manually operated shut-off ball valve, OEM P/N 009G7022. Used to isolate liquid, suction and hot-gas lines in commercial refrigeration and air-conditioning systems. Straightway, bi-flow design with solder ODF connections, 1/2 in inlet and outlet. Brass valve body with copper connections and a brass cap with wire seal. Max working pressure 45 bar (650 psig); media temperature -40 °C to 100 °C. Refrigerant compatibility is listed below and on the datasheet — verify against your system charge.

Technical Specifications

BrandDanfoss
Part number009G7022
ModelGBC 12s shut-off (stop) ball valve
CategoryHVAC & Refrigeration — Ball Valves
DirectionStraightway
FlowBi-flow (no installation direction)
ConnectionSolder, ODF, 1/2 in, inlet and outlet
Max working pressure (PS/MWP)45 bar (650 psig)
Media temperature range-40 °C to 100 °C (-40 °F to 212 °F)
Kv12.92 m³/h
Cv14.94 gal/min
Net weight0.261 kg
Gross weight0.292 kg
MaterialsValve body brass; connection copper; cap with wire seal
ApprovalsC UL US Listed, EAC, CE
Refrigerant compatibilityR134a, R22, R32, R404A, R407A, R407C, R407F, R410A, R448A, R449A, R450A, R452A, R507A, R513A, R1234ze(E)
Code number009G7022
Product typeGBC 12s
Product groupShut-off and regulating valves
Body materialBrass
Connection materialCopper
Inlet connection typeSolder, ODF
Inlet size1/2 in
Outlet connection typeSolder, ODF
Outlet size1/2 in
Cv value14.940 gal/min
Temperature range-40 °C to 100 °C
RefrigerantsR1234ze(E); R134a; R22/R407C; R32; R404A/R507A; R407A; R407F; R410A; R448A; R449A; R450A; R452A; R513A
Fluid Group1; 2
PED categoryArt. 4, par. 3
UL approved refrigerantsR134a; R22; R404A; R407A; R407C; R407F; R410A; R448A; R449A; R450A; R452A; R507A; R513A
UL markYes
CE markYes
REACH candidate-list substancesLead (CAS no. 7439-92-1)
EAN5702428065566
Access portNo
EquipmentCap w. wire seal
Flow directionBi-flow
Flow direction indicatorEmbossed 2-way arrow
Ignition source assessmentYes

Properties

MaterialValve body brass; connection copper — full material breakdown in the GBC datasheet
Pressure rating45 bar (650 psig) max working pressure
Temperature range-40 °C to 100 °C
MOQ1

Compatibility

Manually operated shut-off ball valve for liquid, suction and hot-gas lines in refrigeration and air-conditioning systems. Bi-flow (no installation direction). Solder ODF connections — verify code and connection size before ordering. Image is the genuine Danfoss GBC datasheet product render (size-independent body) shared across the GBC line.

Standards

Approvals

Attached Documents