Danfoss AVTB DN 25 Self-Acting Temperature Controller 50 °C – 90 °C

Danfoss · HVAC & Refrigeration · Water Regulating Valves · Denmark · danfoss.com
Part Number
003N8272  ·  HS 8481.80
Danfoss AVTB DN 25 Self-Acting Temperature Controller 50 °C – 90 °C

Danfoss AVTB self-acting temperature controller, OEM P/N 003N8272, DN 25, PN 16. Proportional self-acting valve that throttles flow to hold a temperature set point without external power; the charged sensor and 2 m capillary act directly on the valve cone. Setting range 50 °C – 90 °C; Kvs 5.5 m³/h; connection NPT 1 (internal thread); brass body CuZn40Pb2; linear flow characteristic; flow or return mounting. Media: district heating/cooling circulation water (pH 7–10). Approved to ETA VA 1.54/18952.

Technical Specifications

BrandDanfoss
Part number003N8272
Type designationAVTB PN 16, DN 25, 5.5 m³/h, 50 °C – 90 °C, 2 m, internal thread NPT
CategoryHVAC & Refrigeration — Water Regulating Valves
Functionself-acting proportional temperature controller (throttles on rising temperature)
Nominal sizeDN 25
Pressure classPN 16
Kvs5.5 m³/h
Temperature setting range50 °C – 90 °C
ConnectionNPT 1 (internal thread)
Capillary tube length2 m
Temperature sensorCopper, Ø18 mm × 210 mm
Flow characteristicLinear
Mounting versionFlow or return
Body materialBrass CuZn40Pb2 (W.-no. 2.0402)
Valve cone / seatNBR / brass
MediaDistrict heating / cooling circulation water (pH 7–10)
Ambient temperature range0 °C to 70 °C
EAN5715255156123
ApprovalsETA VA 1.54/18952; EAC, PED, EU RoHS, China RoHS

Properties

MaterialBody brass CuZn40Pb2 (W.-no. 2.0402); cone/seat NBR / brass; sensor Copper, Ø18 mm × 210 mm
Pressure ratingPN 16
Temperature range50 °C – 90 °C setting range
Standard sizeDN 25
Thread standardANSI/ASME B1.20.1
MOQ1

Compatibility

Install with the sensor in the medium to be controlled; the controller throttles on rising temperature. For district heating/cooling and industrial temperature control. Confirm setting range 50 °C – 90 °C and connection NPT 1 (internal thread) before ordering.

Standards

Approvals