cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Danfoss FJVA 20 Thermostatically Operated Water Valve G 3/4 0–30 °C

Danfoss · HVAC & Refrigeration · Water Regulating Valves · Denmark · danfoss.com
Part Number
003N8244  ·  HS 8481.80
Danfoss FJVA 20 Thermostatically Operated Water Valve G 3/4 0–30 °C

Danfoss FJVA 20 thermostatically operated cooling-water valve, OEM P/N 003N8244. Self-acting valve that regulates the flow of condenser cooling water from the water temperature — the entire filled bellows element acts as the temperature sensor, so no separate capillary bulb is required. Opens on rising sensor temperature; fit in the cooling-water return line. Brass body, G (ISO 228-1) 3/4 in internal connection. Kv 3.4 m³/h; orifice 20 mm; bypass 2 mm. Low-range sensor temperature setting 0 – 30 °C. Max working pressure 16 bar; differential pressure 0 – 10 bar; media temperature –25 to 130 °C. Neutral media. Confirm the setting range and code against the datasheet before ordering.

Technical Specifications

BrandDanfoss
Part number003N8244
ModelFJVA 20 thermostatically operated water valve (low range)
CategoryHVAC & Refrigeration — Water Regulating Valves
Versionself-acting condenser cooling-water valve, filled bellows sensor (no separate bulb), internal thread
Functionopens on rising sensor temperature; regulates condenser cooling-water flow
Nominal sizeDN 20
Connectioninternal thread G 3/4 in (ISO 228-1)
Orifice size20 mm
Bypass diameter2 mm
Kv3.4 m³/h (Cv 3.9 gal/min)
Sensor temperature setting range0 – 30 °C (32 – 86 °F)
Media temperature range–25 to 130 °C (–13 to 266 °F)
Max working pressure16 bar (232 psig)
Differential pressure range0 – 10 bar (0 – 145 psi)
Body materialbrass
Medianeutral media
PackingMulti pack (10 pcs)
EAN5702423028931
ApprovalsEAC, PED, EU RoHS, China RoHS, LLC CDC TYSK

Properties

MaterialBrass body; filled bellows temperature element
Pressure ratingMax working pressure 16 bar; differential pressure 0 – 10 bar
Temperature range–25 to 130 °C (media); setting 0 – 30 °C
Standard sizeDN 20
Thread standardISO 228-1 (G)
MOQ1

Compatibility

Fit in the condenser cooling-water return line so the bellows senses the water temperature; opens on rising temperature. Self-acting (no external power or capillary bulb). Confirm code and setting range before ordering.

Standards

Approvals

Attached Documents