Danfoss WVO 10 pressure-operated water regulating valve, OEM P/N 003N8053. Modulates condenser cooling-water flow to hold the condensing pressure constant and shuts the water off when the plant stops: the valve is opened by the condensing (refrigerant) pressure on a bellows and closed by an adjustable spring. Opens on rising cond. pressure. Control pressure range 8 bar – 12 bar. Water connection 3/8 in G (ISO 228-1); refrigerant sensing 1/4 in - 6 mm Solder, ODF. Kv 0.63 m³/h. Body Brass. Max working pressure 16 bar (232 psig). Media Fresh water. OEM designation "". OEM P/N 003N8053. EAN 5702428976015. Technical data quoted verbatim from store.danfoss.com (code 003N8053).
| Brand | Danfoss |
| Part number | 003N8053 |
| Model | WVO 10 |
| Category | HVAC & Refrigeration — Water Regulating Valves |
| Function | Pressure-operated water regulating valve (condenser) |
| Nominal size | WVO 10 (DN 10) |
| Opening configuration | Opens on rising cond. pressure |
| Control pressure range | 8 bar – 12 bar |
| Water connection size | 3/8 in G |
| Connection standard | ISO 228-1 |
| Refrigerant sensing connection | 1/4 in - 6 mm Solder, ODF |
| Capillary tube length | 900 mm |
| Kv value | 0.63 m³/h (Cv 0.7 gal/min) |
| Orifice size | 10 mm (2/5 in) |
| Max differential pressure | 10 bar |
| Max working pressure | 16 bar (232 psig) |
| Max test pressure | 24 bar |
| Body material | Brass |
| Lubricants | Oilfree applications |
| Refrigerants (sensing side) | R1234yf R1270 R134a R22 R290 R404A R407A R407C R407F R407H R422B R422D R448A R449A R449B R450A R452A R454A R454C R455A R507A R513A R600 R600a |
| Media | Fresh water |
| Medium temperature range | -25 °C to 130 °C (-13 °F to 266 °F) |
| Approvals | UL, PED, EAC, China RoHS, RoHS |
| REACH Candidate List substance | Lead (CAS no. 7439-92-1) |
| Packing | Multi pack (10 pc) |
| Volume | 4.082 L |
| Net weight | 1.051 kg |
| Gross weight | 1.332 kg |
| OEM description | EAN: 5702428976015 |
| HS code | 8481.80 |
| EAN | 5702428976015 |
| Material | Brass |
| Pressure rating | 16 bar (232 psig) max working pressure |
| Temperature range | -25 °C to 130 °C |
| Standard size | WVO 10 |
| Thread standard | ISO 228-1 |
| MOQ | 1 |
Fit in the cooling-water line to the condenser with the flow arrow in the direction of flow; the refrigerant sensing connection goes to the condenser/receiver. Set the closing pressure to the required condensing pressure. Direct-acting (opens on rising pressure). Confirm code, water connection and control-pressure range against the datasheet before ordering.