Danfoss WVFX 25 pressure-operated water valve, OEM P/N 003N8025. Regulates the flow of cooling water to a water-cooled condenser from the condensing (refrigerant) pressure and shuts the water off when the plant stops. Opens on rising condensing pressure; narrow control-pressure band set on the adjustment spring. Brass body, NPT (ANSI/ASME B1.20.1) water connection. Water connection NPT 1-11.5 in; refrigerant sensing connection 1/4 in / 6 mm SAE flare, 800 mm capillary. Control pressure range 4 – 23 bar; Kv 5.5 m³/h. Body brass. Max working pressure 16 bar (232 psig). Media: Fresh water, neutral brine. 800 mm capillary tube for remote sensing. Verify the setting range and refrigerant against the datasheet before ordering.
| Brand | Danfoss |
| Part number | 003N8025 |
| Model | WVFX 25 pressure-operated water valve |
| Category | HVAC & Refrigeration — Water Regulating Valves |
| Version | wide modulating range, capillary (800 mm) remote-mount, NPT water connection |
| Function | opens on rising condensing (refrigerant) pressure; narrow-band regulation of condensing pressure by throttling the condenser cooling water |
| Nominal size | WVFX 25 (DN 25) |
| Water-side connection | NPT 1-11.5 in, NPT (ANSI/ASME B1.20.1) (inlet and outlet) |
| Refrigerant sensing connection | 1/4 in / 6 mm SAE flare, 800 mm capillary |
| Control pressure range | 4 – 23 bar |
| Kv | 5.5 m³/h |
| Max working pressure (MWP) | 16 bar (232 psig) water side |
| Media temperature range | -25 °C to 130 °C |
| Orifice | 25 mm |
| Body material | brass |
| Media | Fresh water, neutral brine |
| Packing | Multi-pack (10 pcs) |
| EAN | 5702428866828 |
| Materials | Valve housing hot-pressed brass; regulating seat and bellows stainless steel; adjustment spring steel |
| Approvals | UL Listed (C UL US), EAC, PED, EU RoHS, China RoHS |
| Material | Valve housing hot-pressed brass; regulating seat and bellows stainless steel; adjustment spring steel |
| Pressure rating | 16 bar (232 psig) water side max working pressure |
| Temperature range | -25 °C to 130 °C |
| Standard size | WVFX 25 |
| Thread standard | ANSI/ASME B1.20.1 |
| MOQ | 1 |
Fit in the cooling-water line to the condenser with the flow arrow in the direction of flow; the refrigerant sensing flare connects to the condenser/receiver. Set the closing pressure on the adjustment spring to the required condensing pressure. Direct-acting (opens on rising pressure). Confirm code, water connection and setting range before ordering.