Danfoss AVTB self-acting thermostatic temperature controller, OEM P/N 003N7252. A proportional, self-acting (no external power) valve that throttles the flow to hold a set medium temperature: the liquid-charged sensor closes the valve on rising temperature. Valve size DN 20. Kvs 3.4 m³/h. Temperature setting range 20 °C – 60 °C. Connection NPT 3/4. PN 16. Body Brass CuZn40Pb2 W. no 2.0402. OEM designation "AVTB 20 Thermostatic valve 20-60 °C". OEM P/N 003N7252. EAN 5715255156185. Technical data quoted verbatim from store.danfoss.com (code 003N7252).
| Brand | Danfoss |
| Part number | 003N7252 |
| Model | AVTB (fast) |
| Category | HVAC & Refrigeration — Water Regulating Valves |
| Function | Self-acting thermostatic temperature controller |
| Valve size | DN 20 |
| Valve diameter | 20 mm |
| Temperature setting range | 20 °C – 60 °C |
| Kvs value | 3.4 m³/h |
| Connection size | NPT 3/4 |
| Connection type | Internal thread |
| Sensor connection | M14x1 / R1/2 ext thread acc. DIN 2999 |
| Temperature sensor length | 180 mm |
| Temperature sensor diameter | 9.5 mm |
| Capillary tube length | 2 m |
| Max differential pressure | 10 bar |
| Flow characteristic | Linear |
| Cone/seat sealing material | NBR / Brass W. No 2.0402 |
| Valve body material | Brass CuZn40Pb2 W. no 2.0402 |
| Valve seat material | Cr Ni steel W.no 1.4301 |
| Temperature sensor material | Copper mat. No 2.0090 |
| Approval standard | ETA VA 1.54/18952 |
| Media | District heating/cooling circulation water |
| Medium temperature range | 2 °C to 130 °C |
| Body material | Brass CuZn40Pb2 W. no 2.0402 |
| Approvals | Approval standard ETA VA 1.54/18952 |
| REACH Candidate List substance | Lead (CAS no. 7439-92-1) |
| Volume | 4.082 L |
| Net weight | 1.634 kg |
| Gross weight | 1.72 kg |
| OEM description | AVTB 20 Thermostatic valve 20-60 °C |
| EAN | 5715255156185 |
| HS code | 8481.80 |
| Material | Brass CuZn40Pb2 W. no 2.0402 |
| Pressure rating | PN 16; max differential pressure 10 bar |
| Temperature range | 2 °C to 130 °C (media); setting range 20 °C–60 °C |
| Standard size | AVTB (fast) |
| MOQ | 1 |
Fit in the flow line with the sensor in the medium to be controlled; the AVTB closes on rising temperature. Match valve size (DN 20), Kvs (3.4 m³/h) and temperature setting range to the application before ordering. Self-acting — no external power or actuator required. Confirm code and range before ordering.