Danfoss Thermostatic Water Valve AVTA 15 — G 1/2, Mass Charge 0–30 °C

Danfoss · HVAC & Refrigeration · Water Regulating Valves · Denmark · danfoss.com
Part Number
003N0042  ·  HS 8481.80
Danfoss Thermostatic Water Valve AVTA 15 — G 1/2, Mass Charge 0–30 °C

Danfoss AVTA 15 thermostatically operated water valve, genuine OEM code 003N0042. Self-acting proportional temperature-regulating valve for cooling-water and heating circuits: it opens on rising sensor temperature and needs no external power supply, compressed air or electricity. Mass charge with a regulating range of 0–30 °C. Connection G 1/2 (ISO 228-1); kv 1.9 m³/h; brass valve body. Pressure-relieved design — the degree of opening is not affected by differential pressure. Supplied complete with capillary tube gland and hermetically sealed thermostatic element (sensor 18 x 210 mm, capillary 2000 mm). Mass charge — the sensor must be installed in an environment warmer than the valve body; short time constant. EAN 5702423002801.

Technical Specifications

BrandDanfoss
Part number003N0042
TypeAVTA 15 — thermostatically operated (self-acting) water regulating valve
CategoryHVAC & Refrigeration — Water Regulating Valves
FunctionOpens on rising sensor temperature (proportional flow regulation)
Charge typeMass
Regulating range0–30 °C
kv value1.9 m³/h
Valve size / orificeDN15 / 15 mm
ConnectionG 1/2 (ISO 228-1)
Body materialBrass
Seat / cone materialEPDM (ethylene-propylene rubber)
Sensor18 x 210 mm
Capillary tube length2000 mm
Max. working pressure (MWP)16 bar (232 psi)
Max. test pressure25 bar (365 psi)
Max. pressure on sensor25 bar (365 psi)
Medium temperature range-25 to 130 °C (-13 to 266 °F)
Mediafresh water or neutral brine (ethylene glycol up to 40%)
Net weight1.146 kg
EAN5702423002801
HS code8481.80 (thermostatically controlled valves)

Properties

MaterialBrass
Pressure rating16 bar (232 psi) max working pressure
Temperature rangeRegulating range 0–30 °C; medium -25 to 130 °C
Standard sizeG 1/2
Thread standardG 1/2
MOQ1

Compatibility

Self-acting valve — no power supply required. Select charge type (Mass) and regulating range (0–30 °C) to suit the temperature to be maintained; aim to keep the required sensor temperature near the middle of the range. Install an FV strainer ahead of the valve; route the capillary without kinks.