| Body | PPS, stainless steel |
| Seal | EPDM |
| Cover | PC |
| Display | Graphic display with backlight and intuitive menu navigation |
| Operating keys | Membrane keypad with 4 keys |
| Service interface | Connection to PC via USB büS interface set |
| Configuration tool | Bürkert Communicator PACTware (only for device variants with PROFIBUS or analogue variant with serial interface) |
| Initialisation of positioner/process | Automatically by P.TUNE function (self-optimisation of PID parameter) |
| Manual operation of pilot valve | In manual mode via push-button on control panel |
| Fieldbus | EtherNet/IP, PROFINET, Modbus TCP, PROFIBUS DP-V1 |
| Digital | Bürkert system bus (büS) (based on CANopen) |
| Measurement principle | Linear: inductive Rotary: magnetic |
| Position detection module | Contactless analogue position sensor (wear-free) |
| Valve spindle | Linear: 3...45 mm Rotary: 30...180° |
| Operating voltage | 24 V DC ± 10 % UL: NEC Class 2 |
| Residual ripple | 10 %, no technical DC voltage |
| Power consumption | ≤ 5 W |
| Protection class | III according to DIN EN 61140 (VDE 0140 - 1) |
| Digital input | 1 digital input, 0...5 V = log „0", 10...30 V = log „1" |
| Digital output | 2 digital outputs (optional), galvanically isolated |
| Current limit per digital output | 100 mA, in case of overload, the output is switched off and cyclically switched on again to check for still existing overload. |
| Analogue output | 1 output (optional) 0/4...20 mA, 0...5/10 V |
| Set-point value setting default | 0/4...20 mA 0...5/10 V |
| Input resistance | 0/4...20 mA, 180 Ω 0...5/10 V, 19 kΩ |
| Frequency setting | 17 kΩ input resistance, 0...1000 Hz |
| Pt 100 setting | 20...+ 220 °C, resolution < 0.1 °C |