| Nominal diameter (port connection) | DN 10…DN 100, NPS ⅜…NPS 4 |
| Safety setting in case of power failure | Normally closed (control function A), normally open (control function B) |
| Flow direction | Against closing direction (below seat), with closing direction (above seat) |
| Operating pressure | 0 bar(g)…25 bar(g), 40 bar(g) on reques |
| Nominal pressure | PN 25/PN 40 (DIN EN 1333), Class 150 (DIN EN 1759) |
| Pilot pressure | 2.5 bar(g)…10 bar(g) |
| Seat leakage | Leakage rate A (DIN EN 12266 - 1), seat seal PTFE and PEEK, test medium air |
| KV value | 4.7 m³/h…140 m³/h |
| Medium temperature | - 40 °C…+ 230 °C |
| Viscosity | Max. 600 mm²/s |
| Flange connection | DIN EN 1092 - 1 |
| Threaded connection | G (DIN ISO 228 - 1) |
| Welded connection | DIN EN ISO 1127 / ISO 4200 / DIN 11866 series B |
| Pilot air port | Push-in connector (external Ø 6 mm or ¼") or thread G ⅛" (on request) |
| Material certificate | 2.2, 3.1 |