ABB MS132-0.25 manual motor starter (motor protective circuit breaker), order code 1SAM350000R1002. Current setting range 0.16. 0.25 A, adjustable to the motor full-load current. Three-pole fuseless protection with thermal overload release (trip class 10), electromagnetic short-circuit release and phase-loss sensitivity. Built-in disconnect function, trip-free mechanism, ON/OFF/TRIP indication and lockable rotary handle. Rated operational voltage up to 690 V AC, IP20, 45 mm width, DIN-rail or screw mounting. Supplied as OEM original where available, or a verified compatible equivalent.
| Type | ABB MS132-0.25 |
| Order code | 1SAM350000R1002 |
| Current setting range | 0.16 ... 0.25 A |
| Rated operational current Ie | 0.25 A |
| Motor rating | approx. 0.06 kW at 400 V (3-phase) |
| Power loss | 0.7 W (lower) / 1.7 W (upper) per phase |
| Construction | 3-pole, thermal overload + electromagnetic short-circuit release, fuseless |
| Trip class | 10 (IEC/EN 60947-4-1) |
| Phase-loss sensitivity | yes |
| Functions | disconnect function, trip-free mechanism, ON/OFF/TRIP indication, lockable rotary handle, test function |
| Rated operational voltage Ue | up to 690 V AC |
| Rated insulation voltage Ui | 690 V |
| Rated impulse withstand voltage Uimp | 6 kV |
| Rated frequency | 50/60 Hz |
| Temperature compensation | -25 ... +60 °C |
| Short-circuit breaking | short-circuit proof up to 100 kA; Ics/Icu 100 kA at 400 V AC; 3 kA at 690 V AC |
| Pollution degree | 3 |
| Degree of protection | IP20 |
| Width | 45 mm; DIN-rail or screw mounting |
| Standards | IEC/EN 60947-1, IEC/EN 60947-2, IEC/EN 60947-4-1, UL 508 |
| Temperature range | -25 °C to +60 °C (temperature compensated) |
| IP rating | IP20 |
| MOQ | 1 |
Set the dial to the motor full-load current within the stated range. Verify order code, setting range and any required auxiliary/signal contacts before ordering.