ABB MO165-73 manual motor starter magnetic only (motor protector), order code 1SAM461000R1018. Rated operational current 73 A; rated motor power 37 kW at 400 V AC (AC-3). Three-pole fuseless device with an electromagnetic (instantaneous) short-circuit release only — it has no thermal overload release, so it is combined with a separate overload relay or motor controller for full motor protection. Rated instantaneous short-circuit release setting Ii 1022 A; rated service short-circuit breaking capacity Ics 30 kA at 400 V AC. Built-in disconnect function, trip-free mechanism, ON/OFF/TRIP indication and lockable rotary handle. Rated operational voltage up to 690 V AC, IP20, 55 mm width, DIN-rail or screw mounting. Part of the ABB MS116/MS132/MS165/MO132/MO165 manual-motor-starter range. Supplied as OEM original where available, or a verified compatible equivalent.
| Type | ABB MO165-73 |
| Order code | 1SAM461000R1018 |
| Rated uninterrupted current Iu | 73 A |
| Rated operational current Ie | 73 A |
| Rated motor power at 400 V AC (AC-3) | 37 kW |
| Construction | 3-pole, electromagnetic short-circuit release only (magnetic only), fuseless |
| Overload protection | none — combine with an overload relay or motor controller |
| Rated instantaneous short-circuit release setting Ii | 1022 A |
| Rated service short-circuit breaking capacity Ics at 400 V AC | 30 kA |
| Functions | disconnect function, trip-free mechanism, ON/OFF/TRIP indication, lockable rotary handle |
| Rated operational voltage Ue | up to 690 V AC |
| Rated insulation voltage Ui | 690 V |
| Rated impulse withstand voltage Uimp | 6 kV |
| Rated frequency | 50/60 Hz |
| Degree of protection | IP20 |
| Width | 55 mm; DIN-rail or screw mounting |
| Accessories | auxiliary contacts, signaling contacts, undervoltage releases, shunt trips, 3-phase busbars, power in-feed blocks |
| Standards | IEC/EN 60947-1, IEC/EN 60947-2, IEC/EN 60947-4-1, UL 508 |
| IP rating | IP20 |
| MOQ | 1 |
Magnetic-only short-circuit protection; provide motor overload protection separately. Verify order code and any required auxiliary/signal contacts before ordering.