cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

ABB TF96-60 Thermal Overload Relay 48-60 A for Motor Protection

ABB Automasjon · Switchgear & Protection · Overload Relays
Part Number
TF96-60  ·  HS 8536.49
ABB TF96-60 Thermal Overload Relay 48-60 A for Motor Protection

ABB TF96-60 - the TF96-60 thermal overload relay is an electromechanical protection device for the main circuit. It provides motor protection in the event of overload or phase failure, with trip class 10, temperature compensation, trip contact (NC), signal contact (NO), and selectable automatic or manual reset. A trip-free mechanism, STOP function, and trip indication are included; the relay connects directly to block contactors, and single mounting kits are available as accessories.

Technical Specifications

Manufacturer part number (MPN)TF96-60
EAN / GTIN4013614482991
Sales unitpcs
Setting range48-60 A
Country of OriginIndia
Product Sales StatusActive
Product Net Width69.9 mm
Product Net Height106.9 mm
Product Net Depth / Length106.3 mm
Rated Operational VoltageAuxiliary Circuit 600 V AC/DC; Main Circuit 690 V AC; Main Circuit 440 V DC
Rated Operational Current (I e )60 A
Rated Frequency (f)Auxiliary Circuit 50 Hz; Auxiliary Circuit 60 Hz; Auxiliary Circuit DC; Main Circuit 50 Hz; Main Circuit 60 Hz
Rated Impulse Withstand Voltage (U imp )Auxiliary Circuit 6 kV; Main Circuit 8 kV
Rated Insulation Voltage (U i )690 V
Number of Poles3P
Number of Auxiliary Contacts NC1
Number of Auxiliary Contacts NO1
Number of Protected Poles3
Conventional Free-air Thermal Current (I th )Auxiliary Circuit NC 6 A; Auxiliary Circuit NO 4 A
Rated Operational Current AC-15 (I e )(120 V) NC 3 A; (120 V) NO 0.5 A; (240 V) NC 3 A; (240 V) NO 0.5 A; (400 V) NC 0.75 A; (400 V) NO 0.5 A; (500 V) NC 0.75 A; (500 V) NO 0.5 A
Rated Operational Current DC-13 (I e )(125 V) NC 0.55 A; (125 V) NO 0.55 A; (24 V) NC 1.25 A; (24 V) NO 1.25 A; (250 V) NC 0.27 A; (250 V) NO 0.27 A; (500 V) NC 0.15 A; (500 V) NO 0.15 A; (60 V) NC 0.55 A; (60 V) NO 0.55 A
Degree of ProtectionHousing IP20; Main Circuit Terminals IP10
Pollution Degree3
Connecting Capacity Auxiliary CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²; Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²; Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²; Flexible 1/2x 0.75 ... 1 mm²; Flexible 1/2x 1 ... 2.5 mm²; Rigid 1/2x 0.75 ... 4 mm²
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 6 ... 35 mm²; Flexible with Ferrule 1x 6 ... 50 mm²; Flexible with Insulated Ferrule 1/2x 6 ... 16 mm²; Flexible with Insulated Ferrule 1x 6 ... 50 mm²; Flexible 1/2x 6 ... 35 mm²; Flexible 1x 6 ... 50 mm²; Rigid 1/2x 6 ... 35 mm²; Rigid 1x 6 ... 50 mm²
Tightening TorqueAuxiliary Circuit 1 ... 1.2 N·m; Main Circuit 6.0 ... 9.0 N·m
Wire Stripping LengthAuxiliary Circuit 9 mm; Main Circuit 20 mm
Recommended Screw DriverAuxiliary Circuit Pozidriv 2; Main Circuit Hexagon 4
Mounting Position1 ... 6
Power Lossat Rated Operating Conditions per Pole 3 ... 4.7 W
Suitable ForAF80; AF96
StandardsIEC/EN 60947-1; IEC/EN 60947-4-1; IEC/EN 60947-5-1; UL 60947-1; UL 60947-4-1; IEC 60335-2-40 A2L
Maximum Operating Voltage UL/CSAMain Circuit 600 V AC
Contact Rating UL/CSA(NC:) B600; (NC:) Q600; (NO:) Q600; (NO:) D300
Connecting Capacity Main Circuit UL/CSAFlexible 1x 8-1 AWG; Flexible 2x 8-3 AWG; Stranded 1x 8-1 AWG; Stranded 2x 8-3 AWG
Connecting Capacity Auxiliary Circuit UL/CSAFlexible 1/2x 18-12 AWG; Stranded 1/2x 18-12 AWG
Tightening Torque UL/CSAAuxiliary Circuit 9 ... 11 in·lb; Main Circuit 50 ... 80 in·lb
Ambient Air TemperatureOperation -40 ... +70 °C; Operation Compensated -40 ... +70 °C; Storage -50 ... +80 °C
Ambient Air Temperature CompensationYes
Maximum Operating Altitude Permissible2000 m
Resistance to Shock acc. to IEC 60068-2-2711 ms Pulse 25g
Resistance to Vibrations5g 3 ... 150 Hz
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA2CMT2023-006525
ABB EcoSolutionsYes
ABB Site Meeting Group Waste To Landfill TargetUL 2799 Zero Waste To Landfill Validation available
EcoSolutions Profile1SFC100125C0355
End Of Life Disassembling Instructions1SAC200334H0001
Environmental Information1SAC200059H0009
Environmental Product Declaration - EPD1SAC200249H0001
Improved Energy Efficiency for CustomersProduct Efficiency - Product considered more energy-efficient compared to similar product on market or older products from the same line
Recyclability Rate of the Product acc. to EN45555Design for Closing Resource Loops - Standard EN45555 - 93.3 %
A2L Certificate – IEC1SAA941000-4601
ABS Certificate1SAA941003-0101
ATEX Certificate1SAA941006-3901
BV Certificate1SAA941001-0203
CB Certificate1SAA941015-2001
CCC Certificate2024010304636179
CQC CertificateCQC2014010309689434
Declaration of Conformity - CCC2020980309000292
Declaration of Conformity - CE1SAD101100-3503
Declaration of Conformity - UKCA1SAD201100-3503
DNV GL Certificate1SAA941004-0301
EAC Certificate1SAA941002-2701
IECEx Certificate1SAA941002-4001
LR Certificate1SAA941003-0501
RINA CertificateRINA_ELE098115XG
RMRS Certificate1SAA941002-0701
UL CertificateE48139-20130329
Object Classification CodeF
ETIM 9EC000106 - Thermal overload relay
eClassV11.0 : 27371501
UNSPSC39122330
IDEA Granular Category Code (IGCC)5366 >> Thermal overload relay
E-Number (Finland)3706591
E-Number (Norway)4116795
E-Number (Sweden)3210271

Properties

MOQ1

Cross-References

Attached Documents