ABB TF65-47 Thermal Overload Relay 36–47 A, Class 10, 3-Pole

ABB Automasjon · Switchgear & Protection · Overload Relays
Part Number
TF65-47  ·  HS 8536.49
ABB TF65-47 Thermal Overload Relay 36–47 A, Class 10, 3-Pole

ABB TF65-47 — economic electromechanical thermal overload relay for the main circuit, 36–47 A setting range with trip Class 10. Provides reliable overload and phase-failure protection for motors with temperature compensation, NC trip and NO signal contacts, selectable automatic or manual reset, trip-free mechanism, STOP function and trip indication. Connects directly to the block contactors; single-mounting kits are available as accessories.

Technical Specifications

Manufacturer part number (MPN)TF65-47
EAN / GTIN4013614482946
Sales unitpcs
Setting range36-47 A
Configuration OnlyNo
Country of OriginChina
CriticalityNo
Lead Time35 day
NoteNo
Product Availability ClassStandard delivery time
Product Sales StatusActive
Storage Location4001
Product Net Width54.9 mm
Product Net Height101.4 mm
Product Net Depth / Length106.9 mm
Rated Operational VoltageAuxiliary Circuit 600 V AC/DC; Main Circuit 690 V AC; Main Circuit 440 V DC
Rated Operational Current (I e )47 A
Rated Frequency (f)Auxiliary Circuit 50 Hz; Auxiliary Circuit 60 Hz; Auxiliary Circuit DC; Main Circuit 50 Hz; Main Circuit 60 Hz
Rated Impulse Withstand Voltage (U imp )Auxiliary Circuit 6 kV; Main Circuit 8 kV
Rated Insulation Voltage (U i )690 V
Number of Poles3P
Number of Auxiliary Contacts NC1
Number of Auxiliary Contacts NO1
Number of Protected Poles3
Conventional Free-air Thermal Current (I th )Auxiliary Circuit NC 6 A; Auxiliary Circuit NO 4 A
Rated Operational Current AC-15 (I e )(120 V) NC 3 A; (120 V) NO 0.5 A; (240 V) NC 3 A; (240 V) NO 0.5 A; (400 V) NC 0.75 A; (400 V) NO 0.5 A; (500 V) NC 0.75 A; (500 V) NO 0.5 A
Rated Operational Current DC-13 (I e )(125 V) NC 0.55 A; (125 V) NO 0.55 A; (24 V) NC 1.25 A; (24 V) NO 1.25 A; (250 V) NC 0.27 A; (250 V) NO 0.27 A; (500 V) NC 0.15 A; (500 V) NO 0.15 A; (60 V) NC 0.55 A; (60 V) NO 0.55 A
Degree of ProtectionHousing IP20; Main Circuit Terminals IP10
Pollution Degree3
Connecting Capacity Auxiliary CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²; Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²; Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²; Flexible 1/2x 0.75 ... 1 mm²; Flexible 1/2x 1 ... 2.5 mm²; Rigid 1/2x 0.75 ... 4 mm²
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 2.5 ... 10 mm²; Flexible with Ferrule 1x 2.5 ... 35 mm²; Flexible with Insulated Ferrule 1x 2.5 ... 35 mm²; Flexible with Insulated Ferrule 1/2x 2.5 ... 10 mm²; Flexible 1/2x 2.5 ... 16 mm²; Flexible 1x 2.5 ... 35 mm²; Rigid 1/2x 2.5 ... 16 mm²; Rigid 1x 2.5 ... 35 mm²
Tightening TorqueAuxiliary Circuit 1 ... 1.2 N·m; Main Circuit 4.0 ... 4.5 N·m
Wire Stripping LengthAuxiliary Circuit 9 mm; Main Circuit 17 mm
Recommended Screw DriverAuxiliary Circuit Pozidriv 2; Main Circuit Pozidriv 2
Mounting Position1 ... 6
Power Lossat Rated Operating Conditions per Pole 2.1 ... 3.6 W
Suitable ForAF40; AF52; AF65
StandardsIEC/EN 60947-1; IEC/EN 60947-4-1; IEC/EN 60947-5-1; UL 60947-1; UL 60947-4-1; IEC 60335-2-40 A2L
Maximum Operating Voltage UL/CSAMain Circuit 600 V AC
Contact Rating UL/CSA(NC:) B600; (NC:) Q600; (NO:) Q600; (NO:) D300
Connecting Capacity Main Circuit UL/CSAFlexible 1x 12-2 AWG; Flexible 2x 12-6 AWG; Stranded 1x 12-2 AWG; Stranded 2x 12-6 AWG
Connecting Capacity Auxiliary Circuit UL/CSAFlexible 1/2x 18-12 AWG; Stranded 1/2x 18-12 AWG
Tightening Torque UL/CSAAuxiliary Circuit 9 ... 11 in·lb; Main Circuit 35 ... 40 in·lb
Ambient Air TemperatureOperation -40 ... +70 °C; Operation Compensated -40 ... +70 °C; Storage -50 ... +80 °C
Ambient Air Temperature CompensationYes
Maximum Operating Altitude Permissible2000 m
Resistance to Shock acc. to IEC 60068-2-2711 ms Pulse 25g
Resistance to Vibrations5g 3 ... 150 Hz
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA2CMT2023-006525
ABB EcoSolutionsYes
ABB Site Meeting Group Waste To Landfill TargetUL 2799 Zero Waste To Landfill Validation available
EcoSolutions Profile1SFC100125C0355
End Of Life Disassembling Instructions1SAC200334H0001
Environmental Information1SAC200058H0009
Environmental Product Declaration - EPD1SAC200249H0001
Improved Energy Efficiency for CustomersProduct Efficiency - Product considered more energy-efficient compared to similar product on market or older products from the same line
Recyclability Rate of the Product acc. to EN45555Design for Closing Resource Loops - Standard EN45555 - 93.3 %
A2L Certificate – IEC1SAA941000-4601
ABS Certificate1SAA941003-0101
ATEX Certificate1SAA941005-3901
BV Certificate1SAA941001-0203
CB Certificate1SAA941015-2001
CCC Certificate2024010304636179
CQC CertificateCQC2014010309689432
Declaration of Conformity - CCC2020980309000291
Declaration of Conformity - CE1SAD101100-3503
Declaration of Conformity - UKCA1SAD201100-3503
DNV GL Certificate1SAA941004-0301
EAC Certificate1SAA941002-2701
IECEx Certificate1SAA941001-4001
LR Certificate1SAA941003-0501
RINA CertificateRINA_ELE098115XG
RMRS Certificate1SAA941002-0701
UL CertificateE48139-20130329
Object Classification CodeF
ETIM 9EC000106 - Thermal overload relay
eClassV11.0 : 27371501
UNSPSC39122330
IDEA Granular Category Code (IGCC)5366 >> Thermal overload relay
E-Number (Finland)3706586
E-Number (Norway)4116789
E-Number (Sweden)3210266