ABB 2CDL240114R1648 PS 4/48/16NH A Busbar

ABB Automasjon · Electrical Components · Busbar Systems
Part Number
2CDL240114R1648  ·  HS 8538.90
ABB 2CDL240114R1648 PS 4/48/16NH A Busbar

ABB 2CDL240114R1648 — PS 4/48/16NH A Busbar.

Technical Specifications

Manufacturer part number (MPN)2CDL240114R1648
EAN / GTIN4016779656160
Sales unitpcs
Package quantity10 pcs
Sub-Functioncross wiring for neutral conductor
Suitable ForS200; F200; DDA200
Suitable for Product Class2-pole devices + auxiliary contact
Pitch17.5
Number of Poles48P
Number of Phases4-phase
Number of Mountable Devices12
Number of Terminals (N term )48
Accessory TypeBusbar
Connection TypePin
Options ProvidedNHA
Rated Cross-Section16 mm²
Rated Operational Voltage230 / 400 V AC; Maximum 690 V
Rated Short-time Withstand Current Low Voltage (I cw )25 kA
Rated Uninterrupted Current (I u )80 A
Rated Frequency (f)50 / 60 Hz; DC
Overvoltage CategoryIII
RAL NumberRAL 7035 - Light Grey
Colorgrey
Pollution Degree2
Width in Number of Modular Spacings60
Product Net Width20.4 mm
Product Net Height30.5 mm
Product Net Depth / Length1047 mm
Declaration of Conformity - CE9AKK108469A0841
Declaration of Conformity - UKCA9AKK108469A0914
Instructions and Manuals2CSC400002D0208
Mounting Positionany
ETIM 9EC000215 - Phase busbar
UNSPSC39121117
eClassV11.0 : 27371306
IDEA Granular Category Code (IGCC)4378 >> Phase buss bar
Object Classification CodeW
StandardsIEC/EN 60947-1
ColourGrey
InsulatedYes
Cross section16 mm²
Rated permanent current Iu80 A
Length1047 mm
Conditioned rated short-circuit current Iq25 kA
Rated surge voltage4.5 kV
Type of electric connectionPin
Rated short-time withstand current lcw25 kA
Suitable for devices with auxiliary switchYes
Suitable for devices with N-conductorYes
Suitable for number of devices12
Max. rated operation voltage Ue690 V
Module width17.5 mm
Country of originGermany

Properties

MOQ1

Cross-References