cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Earth-fault RCD DS204 M A-C40/0,03 (2CSR274101R1404)

ABB Automasjon · Electrical Components · RCDs & RCBOs
Part Number
2CSR274101R1404  ·  HS 8536.30
Earth-fault RCD DS204 M A-C40/0,03 (2CSR274101R1404)

ABB 2CSR274101R1404 — The RCBOs DS200 series has the function to protect against overload and short-circuit currents; protection against the effects of sinusoidal alternating earth fault currents; protection against indirect contacts and additional protection aganist direct contacts.

Technical Specifications

Manufacturer part number (MPN)2CSR274101R1404
EAN / GTIN8012542851202
Sales unitpcs
Type of Residual CurrentType A
Rated Ultimate Short-Circuit Breaking Capacity (I cu )(400 V AC) 15 kA
Power Supply ConnectionArbitrary
Electrical Endurance10000 cycle
Number of Protected Poles4
Number of Poles4P
Number of Earth Leakage Circuit Breakers (ELCBs)1
Operating CharacteristicInstantaneous
Position of Neutral TerminalsRight; Left
Release TypeC
Options ProvidedNone
Accessories AvailableYes
Connecting CapacityBusbar 10 mm²; Rigid 16 ... 25 mm²; Flexible 16 ... 25 mm²
Short-Circuit Current Rating (SCCR)30 mA
Tripping CharacteristicC
Rated Voltage (U r )400 V AC
Rated Operational Voltage400 V AC
Rated Current (I n )40 A
Rated Residual Current30 mA
Rated Short-Circuit Capacity(400 V AC) 10 kA
Maximum Breaking Capacity10 kA
Rated Frequency (f)50 … 60 Hz
Power LossTotal 21.6 W
Ambient Air TemperatureOperation -25 ... +55 °C; Storage -40 ... +70 °C
Resistance to Vibrations20 Cycles with Load 0.8 In: 1g or 0.1mm 5...150...5 Hz
Resistance to Shock acc. to IEC 60068-2-2725g 2 shocks 13 ms
Environmental InformationRefer to RoHS
Product Net Width105 mm
Product Net Height93 mm
Product Net Depth / Length69 mm
EPLAN Data9AAC126543_EPLAN
Declaration of Conformity - CE9AKK106713A5607
Instructions and Manuals9AKK107045A1451
ETIM 9EC002281 - Distributor assembly with combination RCCB/MCB
UNSPSC39121601
eClassV11.0 : 27400618
Object Classification CodeF
StandardsIEC/EN 60947-2; IEC/EN 61009-1
Rated fault current0.03 A
Leakage current typeA
Rated short-circuit breaking capacity according to EN 6089810 kA
Current limiting class3
Voltage typeAC
Frequency50/60 Hz
Release characteristicC
Concurrently switching neutral conductorNo
Overvoltage category3
Pollution degree2
Width in number of modular spacings6
Built-in depth73 mm
Degree of protection (IP)IP20
Mounting methodDIN rail
Country of originItaly

Properties

MOQ1

Cross-References

Attached Documents