Safety Switch OTE36T4M 45A 4P EMC (1SCA022613R2600)

ABB Automasjon · Switchgear & Protection · Disconnect Switches
Part Number
1SCA022613R2600  ·  HS 8536.30
Safety Switch OTE36T4M 45A 4P EMC (1SCA022613R2600)

ABB 1SCA022613R2600 — EMC safety switch, 4-p. 415V AC23 45A, 22kW. Mounted auxiliary contact: 1NO0NC. Plastic enclosure. IP65. Black Selector handle. Interlocked cover. Defeatable interlocking. The enclosure in the OTE series is using a rigid glass reinforced polycarbonate enclosure. The enclosure is UV protected, protected against low-pressure water jets (IP65), and hence built for outdoor and indoor use. The cable entries are threaded and have knock out holes for 2 parallell cables and one control cable, both from top and bottom. The handle is padlockable and made for three padlocks. The interlocking can be by-passed, for thermographing etc. The switch is made for 5 wire system, and have a fixed neutral terminal and PE terminal. The EMC protection is utilized by a metal plate in the bottom, connected to the cable shield with clamps, included in the delivery. No EMC glands needed.

Technical Specifications

Manufacturer part number (MPN)1SCA022613R2600
EAN / GTIN6417019199702
Sales unitpcs
Number of poles4P
Degree of Protectionacc. to IEC 60529 IP65
Pollution Degree3
Product Net Width145 mm
Product Net Height200 mm
Product Net Depth / Length90 mm
Cable Cross-Section1.5 ... 35 mm²
Cable Entry PositionTop/Bottom
Cable Outlets Per Side2xM32+M16 / 2xM32+M16
ColorRAL7035
Connecting Capacity Main CircuitScrew Clamp 1.5 ... 35 mm²; Screw Clamp / PE Terminal 2pc 1.5 ... 35 mm²
Conventional Thermal Current (I the )Fully Enclosed 80 A
Enclosure MaterialPlastic
Handle ColorBlack
Handle TypeSelector
Impact Resistance RatingHousing IK08
Maximum Mounted Auxiliary Contacts2 NO, 2 NC
Mounted Auxiliary Contacts1 NO, 0 NC
Neutral TypeFixed and Switchable Neutral
Number of Auxiliary Contacts NC0
Number of Auxiliary Contacts NO1
Position of Line TerminalsTop In - Bottom Out
Position of Neutral TerminalsTop In - Bottom Out
Position of PE TerminalsTop In - Bottom Out
Power Lossat Rated Operating Conditions per Pole 2.8 W; Total 8.4 W
Rated Insulation Voltage (U i )acc. to IEC/EN 60664-1 750 V
Rated Operational Current AC-21A (I e )(400 V) 63 A; (500 V) 63 A; (690 V) 63 A
Rated Operational Current AC-22A (I e )(380 ... 415 V) 63 A; (500 V) 63 A; (690 V) 63 A
Rated Operational Current AC-23A (I e )(380 ... 415 V) 45 A; (500 V) 45 A; (690 V) 20 A
Rated Operational Power AC-23A (P e )(380 ... 415 V) 22 kW; (500 V) 22 kW; (690 V) 15 kW
Rated Operational VoltageMain Circuit 750 V
Rated Short-Circuit Making Capacity (I cm )(690 V AC) 2.1 kA
Rated Short-time Withstand Current Low Voltage (I cw )for 1 s 1.5 kA; for 0.2 s 1.5 kA
Recommended Screw DriverMain Circuit Pozidriv 2
Special FunctionsEMC
StandardsIEC 60947-1, -3
Terminal TypeScrew Terminals
Tightening TorqueMain Circuit 2 N·m
Wire Stripping Length13 mm
BV Certificate1SCC340018D0204
Declaration of Conformity - CE1SCC340004D2705
DNV GL Certificate1SCC340045D0203
Object Classification CodeQ
ETIM 9EC000216 - Switch disconnector (low voltage)
ETIM 10EC000216 - Switch disconnector (AC)
UNSPSC39122205
IDEA Granular Category Code (IGCC)5166 >> Safety switch
eClassV11.1 : 27371403
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
E-Number (Norway)1429422