ABB SACE Tmax XT6N 800 Moulded-Case Circuit Breaker — Ekip M Dip LIU, In=800 A, 3-Pole

ABB · Electrical Components · Moulded Case Circuit Breakers · Switzerland · abb.com
Part Number
1SDA100727R1  ·  HS 8536.20
ABB SACE Tmax XT6N 800 Moulded-Case Circuit Breaker — Ekip M Dip LIU, In=800 A, 3-Pole

ABB SACE Tmax XT6N 800 A frame moulded-case circuit breaker (MCCB). Rated uninterrupted current In = 800 A, 3-pole, F/F (front, fixed) terminals. Electronic trip unit Ekip M Dip LIU. Breaking-capacity class N; rated ultimate short-circuit breaking capacity Icu = 36 kA at 415 V AC; rated operational voltage Ue 690 V AC. Conforms to IEC/EN 60947-2. ABB order code 1SDA100727R1, EAN 8056221003520, ABB/SAP material 1200638408, catalogue code 83052918.

Technical Specifications

ManufacturerABB
Product familySACE Tmax XT6 (moulded-case circuit breaker, IEC 60947-2)
ConfigurationXT6N 800 Ekip M Dip LIU In=800A 3p FF
ABB order code (MPN)1SDA100727R1
EAN / GTIN8056221003520
ABB / SAP material no.1200638408
FrameXT6 (800 A frame)
Breaking-capacity classN
Rated ultimate breaking capacity Icu (415 V AC)36 kA
Trip unitEkip M Dip LIU
Rated uninterrupted current In800 A
Poles3
TerminalsF/F (front, fixed)
Rated operational voltage Ue690 V AC
StandardIEC/EN 60947-2
HS code8536.20
Sales unitpcs

Properties

Primary standardIEC/EN 60947-2
MOQ1

Standards

Cross-References