ABB SACE Tmax XT6N 1000 Moulded-Case Circuit Breaker — Ekip Dip LSI, In=1000 A, 3-Pole

ABB · Electrical Components · Moulded Case Circuit Breakers · Switzerland · abb.com
Part Number
1SDA100722R1  ·  HS 8536.20
ABB SACE Tmax XT6N 1000 Moulded-Case Circuit Breaker — Ekip Dip LSI, In=1000 A, 3-Pole

ABB SACE Tmax XT6N 1000 A frame moulded-case circuit breaker (MCCB). Rated uninterrupted current In = 1000 A, 3-pole, F/F (front, fixed) terminals. Electronic trip unit Ekip Dip LSI (L overload, S short-time-delay, I instantaneous protection). Breaking-capacity class N; rated ultimate short-circuit breaking capacity Icu = 36 kA at 415 V AC; rated operational voltage Ue 690 V AC. Conforms to IEC/EN 60947-2. ABB order code 1SDA100722R1, EAN 8056221007986, ABB/SAP material 1200638410, catalogue code 83052943.

Technical Specifications

ManufacturerABB
Product familySACE Tmax XT6 (moulded-case circuit breaker, IEC 60947-2)
ConfigurationXT6N 1000 Ekip Dip LSI In=1000 3p FF
ABB order code (MPN)1SDA100722R1
EAN / GTIN8056221007986
ABB / SAP material no.1200638410
FrameXT6 (1000 A frame)
Breaking-capacity classN
Rated ultimate breaking capacity Icu (415 V AC)36 kA
Trip unitEkip Dip LSI
Rated uninterrupted current In1000 A
Poles3
TerminalsF/F (front, fixed)
Rated operational voltage Ue690 V AC
StandardIEC/EN 60947-2
HS code8536.20
Sales unitpcs

Properties

Primary standardIEC/EN 60947-2
MOQ1

Standards

Cross-References