ABB SACE Tmax XT2V 160 Moulded-Case Circuit Breaker — MA 160 Im=960, In=160 A, 3-Pole

ABB · Electrical Components · Moulded Case Circuit Breakers · Switzerland · abb.com
Part Number
1SDA076537R1  ·  HS 8536.20
ABB SACE Tmax XT2V 160 Moulded-Case Circuit Breaker — MA 160 Im=960, In=160 A, 3-Pole

ABB SACE Tmax XT2V 160 A frame moulded-case circuit breaker (MCCB). Rated uninterrupted current In = 160 A, 3-pole, F/F (front, fixed) terminals. Magnetic-only trip unit MA 160 Im=960 (magnetic instantaneous short-circuit release, for motor protection). Breaking-capacity class V; rated ultimate short-circuit breaking capacity Icu = 150 kA at 415 V AC; rated operational voltage Ue 690 V AC. Conforms to IEC/EN 60947-2. ABB order code 1SDA076537R1, EAN 8015644812720, ABB/SAP material 1200637571, catalogue code 83051671.

Technical Specifications

ManufacturerABB
Product familySACE Tmax XT2 (moulded-case circuit breaker, IEC 60947-2)
ConfigurationXT2V 160 MA 160 Im=960...2240 3p FF
ABB order code (MPN)1SDA076537R1
EAN / GTIN8015644812720
ABB / SAP material no.1200637571
FrameXT2 (160 A frame)
Breaking-capacity classV
Rated ultimate breaking capacity Icu (415 V AC)150 kA
Trip unitMA 160 Im=960
Rated uninterrupted current In160 A
Poles3
TerminalsF/F (front, fixed)
Rated operational voltage Ue690 V AC
StandardIEC/EN 60947-2
HS code8536.20
Sales unitpcs

Properties

Primary standardIEC/EN 60947-2
MOQ1

Standards

Cross-References