ABB SACE Tmax XT2H 160 Moulded-Case Circuit Breaker — TMA 80-800, In=80 A, 3-Pole

ABB · Electrical Components · Moulded Case Circuit Breakers · Switzerland · abb.com
Part Number
1SDA067601R1  ·  HS 8536.20
ABB SACE Tmax XT2H 160 Moulded-Case Circuit Breaker — TMA 80-800, In=80 A, 3-Pole

ABB SACE Tmax XT2H 160 A frame moulded-case circuit breaker (MCCB). Rated uninterrupted current In = 80 A, 3-pole, F/F (front, fixed) terminals. Thermomagnetic trip unit TMA 80-800 (adjustable thermal overload and magnetic short-circuit release). Breaking-capacity class H; rated ultimate short-circuit breaking capacity Icu = 70 kA at 415 V AC; rated operational voltage Ue 690 V AC. Conforms to IEC/EN 60947-2. ABB order code 1SDA067601R1, EAN 8015644014971, ABB/SAP material 1200637035, catalogue code 83055149.

Technical Specifications

ManufacturerABB
Product familySACE Tmax XT2 (moulded-case circuit breaker, IEC 60947-2)
ConfigurationXT2H 160 TMA 80-800 3p FF
ABB order code (MPN)1SDA067601R1
EAN / GTIN8015644014971
ABB / SAP material no.1200637035
FrameXT2 (160 A frame)
Breaking-capacity classH
Rated ultimate breaking capacity Icu (415 V AC)70 kA
Trip unitTMA 80-800
Rated uninterrupted current In80 A
Poles3
TerminalsF/F (front, fixed)
Rated operational voltage Ue690 V AC
StandardIEC/EN 60947-2
HS code8536.20
Sales unitpcs

Properties

Primary standardIEC/EN 60947-2
MOQ1

Standards

Cross-References