ABB SACE Tmax XT1N 160 Moulded-Case Circuit Breaker — TMD 63-630, In=63 A, 3-Pole

ABB · Electrical Components · Moulded Case Circuit Breakers · Switzerland · abb.com
Part Number
XT1N 160 TMD 63-630 3p F F  ·  HS 8536.20
ABB SACE Tmax XT1N 160 Moulded-Case Circuit Breaker — TMD 63-630, In=63 A, 3-Pole

ABB SACE Tmax XT1N 160 A frame moulded-case circuit breaker (MCCB). Rated uninterrupted current In = 63 A, 3-pole, F/F (front, fixed) terminals. Thermomagnetic trip unit TMD 63-630 (adjustable thermal overload and magnetic short-circuit release). Breaking-capacity class N; rated ultimate short-circuit breaking capacity Icu = 36 kA at 415 V AC; rated operational voltage Ue 690 V AC. Conforms to IEC/EN 60947-2. EAN 8015644013080, ABB/SAP material 1000488010, catalogue code 8601018.

Technical Specifications

ManufacturerABB
Product familySACE Tmax XT1 (moulded-case circuit breaker, IEC 60947-2)
ConfigurationXT1N 160 TMD 63-630 3p FF
EAN / GTIN8015644013080
ABB / SAP material no.1000488010
FrameXT1 (160 A frame)
Breaking-capacity classN
Rated ultimate breaking capacity Icu (415 V AC)36 kA
Trip unitTMD 63-630
Rated uninterrupted current In63 A
Poles3
TerminalsF/F (front, fixed)
Rated operational voltage Ue690 V AC
StandardIEC/EN 60947-2
HS code8536.20
Sales unitpcs

Properties

Primary standardIEC/EN 60947-2
MOQ1

Standards

Cross-References