Part Number
OT160G03P  ·  HS 8536.50
Switch-disconnector OT160G03P

ABB OT160G03P — 3-pole, front operated, base mounted switch-disconnector with protected clamp terminals and with black IP65 handle and shaft.

Technical Specifications

Manufacturer part number (MPN)OT160G03P
EAN / GTIN6417019638706
Sales unitpcs
Country of OriginIndia
Product Sales StatusActive
End Of Life Disassembling Instructions1SCC301116M0201
Environmental Information1SCC301267D0201
Environmental Product Declaration - EPD1SCC301281D0201
Degree of ProtectionFront IP20
Pollution Degree3
Product Net Width123 mm
Product Net Height130 mm
Product Net Depth / Length73 mm
Cable Cross-SectionCu 10 ... 70 mm²
ColorGrey
Conventional Free-air Thermal Current (I th )Θ = 40 °C 160 A
Conventional Thermal Current (I the )Fully Enclosed 160 A
Distance Between PhasesStandard
Handle ColorBlack
Mechanical Durability20000
Mounting TypeBase mounting
Number of Poles3P
Operating ModeFront and Side
Position of Line TerminalsTop In - Bottom Out; Bottom In - Top Out
Power Lossat Rated Operating Conditions per Pole 6.5 W
Rated Conditional Short-Circuit Current (I nc )(200 A fuse, 500 V) 100 kA; (200 A fuse, 690 V) 50 kA
Rated Impulse Withstand Voltage (U imp )12 kV
Rated Insulation Voltage (U i )acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-21A (I e )(380 ... 415 V) 160 A; (500 V) 160 A; (690 V) 160 A
Rated Operational Current AC-22A (I e )(380 ... 415 V) 160 A; (500 V) 160 A; (690 V) 160 A
Rated Operational Current AC-23A (I e )(380 ... 415 V) 160 A; (500 V) 160 A; (690 V) 160 A
Rated Operational Power AC-23A (P e )(220 ... 240 V) 45 kW; (400 ... 415 V) 75 kW; (500 V) 90 kW; (690 V) 132 kW
Rated Operational VoltageMain Circuit 1000 V
Rated Short-Circuit Making Capacity (I cm )(690 V) 12 kA
Rated Short-time Withstand Current Low Voltage (I cw )for 1 s 4 kA
Special FunctionsNo
StandardsIEC 60947-3 / UL 98 / CSA C22.2 NO.4
Switches Operating MechanismMechanism at the End of the Switch; 03 (Left Side)
Terminal TypeScrew Terminals
Tightening Torqueacc. IEC 60947-1 6 N·m
Maximum Operating Voltage UL/CSA600 V
Ampere Rating125 A
Horsepower Rating UL/CSA(240 V AC) Single Phase 20 Hp; (440 ... 480 V AC) Single Phase 30 Hp
Tightening Torque UL/CSA53 in·lb
A2L Certificate – IEC1SCC301336D0201
ATEX CertificateNo certification needed
Declaration of Conformity - CE1SCC301210D2701
DNV GL Certificate1SCC301174D0204
UL CertificatecULus certificate OT160G
VDE CertificateNo certification needed
Object Classification CodeQ
ETIM 9EC000216 - Switch disconnector (low voltage)
ETIM 10EC000216 - Switch disconnector (AC)
UNSPSC39122233
IDEA Granular Category Code (IGCC)5290 >> Disconnect switch
eClassV11.1 : 27371403
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
E-Number (Finland)3638769
E-Number (Norway)4372122
E-Number (Sweden)3171058

Properties

MOQ1

Cross-References

Attached Documents