ABB SACE Tmax XT2N 160 A frame moulded-case circuit breaker (MCCB). Rated uninterrupted current In = 160 A, 4-pole, F/F (front, fixed) terminals. Thermomagnetic trip unit TMA R160 (adjustable thermal overload and magnetic short-circuit release). Breaking-capacity class N; rated ultimate short-circuit breaking capacity Icu = 36 kA at 415 V AC; rated operational voltage Ue 690 V AC; neutral pole rated 100% of In. Conforms to IEC/EN 60947-2. ABB order code 1SDA067043R1, EAN 8015644009496, ABB/SAP material 1000669189, catalogue code 8533854.
| Manufacturer | ABB |
| Product family | SACE Tmax XT2 (moulded-case circuit breaker, IEC 60947-2) |
| Configuration | XT2N 160 TMA R160 4p FF InN=100% |
| ABB order code (MPN) | 1SDA067043R1 |
| EAN / GTIN | 8015644009496 |
| ABB / SAP material no. | 1000669189 |
| Frame | XT2 (160 A frame) |
| Breaking-capacity class | N |
| Rated ultimate breaking capacity Icu (415 V AC) | 36 kA |
| Trip unit | TMA R160 |
| Rated uninterrupted current In | 160 A |
| Poles | 4 |
| Neutral pole rating | 100% of In |
| Terminals | F/F (front, fixed) |
| Rated operational voltage Ue | 690 V AC |
| Standard | IEC/EN 60947-2 |
| HS code | 8536.20 |
| Sales unit | pcs |
| Primary standard | IEC/EN 60947-2 |
| MOQ | 1 |