ABB SACE Tmax XT1S 160 A frame moulded-case circuit breaker (MCCB). Rated uninterrupted current In = 160 A, 4-pole, F/F (front, fixed) terminals. Thermomagnetic trip unit TMD R160 (adjustable thermal overload and magnetic short-circuit release). Breaking-capacity class S; rated ultimate short-circuit breaking capacity Icu = 50 kA at 415 V AC; rated operational voltage Ue 690 V AC; neutral pole rated 100% of In. Conforms to IEC/EN 60947-2. ABB order code 1SDA067446R1, EAN 8015644013400, ABB/SAP material 1200636489, catalogue code 83051028.
| Manufacturer | ABB |
| Product family | SACE Tmax XT1 (moulded-case circuit breaker, IEC 60947-2) |
| Configuration | XT1S 160 TMD R160 4p FF InN=100% |
| ABB order code (MPN) | 1SDA067446R1 |
| EAN / GTIN | 8015644013400 |
| ABB / SAP material no. | 1200636489 |
| Frame | XT1 (160 A frame) |
| Breaking-capacity class | S |
| Rated ultimate breaking capacity Icu (415 V AC) | 50 kA |
| Trip unit | TMD R160 |
| Rated uninterrupted current In | 160 A |
| Poles | 4 |
| Neutral pole rating | 100% of In |
| Terminals | F/F (front, fixed) |
| Rated operational voltage Ue | 690 V AC |
| Standard | IEC/EN 60947-2 |
| HS code | 8536.20 |
| Sales unit | pcs |
| Primary standard | IEC/EN 60947-2 |
| MOQ | 1 |