cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

ABB SACE Tmax XT2N 160 Moulded-Case Circuit Breaker — MA 20, In=20 A

ABB · Electrical Components · Moulded Case Circuit Breakers · Switzerland · abb.com
Part Number
1SDA067049R1  ·  HS 8536.20
ABB SACE Tmax XT2N 160 Moulded-Case Circuit Breaker — MA 20, In=20 A

ABB SACE Tmax XT2N 160 A frame moulded-case circuit breaker (MCCB). Rated uninterrupted current In = 20 A, F/F (front, fixed) terminals. Magnetic-only trip unit MA 20 (magnetic instantaneous short-circuit release, for motor protection). Breaking-capacity class N; rated ultimate short-circuit breaking capacity Icu = 36 kA at 415 V AC; rated operational voltage Ue 690 V AC. Conforms to IEC/EN 60947-2. ABB order code 1SDA067049R1, EAN 8015644009557, ABB/SAP material 1200635944, catalogue code 83052619.

Technical Specifications

ManufacturerABB
Product familySACE Tmax XT2 (moulded-case circuit breaker, IEC 60947-2)
ConfigurationXT2N 160 MA 20 F F
ABB order code (MPN)1SDA067049R1
EAN / GTIN8015644009557
ABB / SAP material no.1200635944
FrameXT2 (160 A frame)
Breaking-capacity classN
Rated ultimate breaking capacity Icu (415 V AC)36 kA
Trip unitMA 20
Rated uninterrupted current In20 A
TerminalsF/F (front, fixed)
Rated operational voltage Ue690 V AC
StandardIEC/EN 60947-2
HS code8536.20
Sales unitpcs

Properties

Primary standardIEC/EN 60947-2
MOQ1

Standards

Cross-References

Attached Documents