| Manufacturer part number (MPN) | PSTX142-600-70 |
| EAN / GTIN | 7320500501467 |
| Sales unit | pcs |
| Rated current | 142 A |
| Country of Origin | Sweden |
| Lead Time | 0 day |
| Product Sales Status | Active |
| Configuration Only | No |
| Criticality | No |
| Note | No |
| Product Availability Class | Only for warranty purposes. Not available for normal sales |
| Storage Location | 4014 |
| Product Net Width | 199 mm |
| Product Net Height | 377 mm |
| Product Net Depth / Length | 283.3 mm |
| Rated Operational Voltage | 208 ... 600 V AC |
| Rated Control Supply Voltage (U s ) | 100 ... 250 V AC |
| Rated Control Circuit Voltage (U c ) | 24 V DC |
| Rated Frequency (f) | 50/60 Hz; Main Circuit 50 / 60 Hz |
| Rated Operational Power - In-Line Connection (Pe) | (230 V) 37 kW; (400 V) 75 kW; (500 V) 90 kW |
| Rated Operational Current - In-Line Connection (Ie) | 142 A |
| Rated Operational Power - Inside Delta Connection | at 230 V 75 kW; at 400 V 132 kW; at 500 V 160 kW |
| Rated Operational Current - Inside Delta Connection | 245 A |
| Service Factor Percentage | 100 % |
| Overload Protection | Built-in electronic overload protection |
| Integrated Electronic Overload | Yes |
| Starting Capacity at Maximum Rated Current Ie | 4xIe for 10s |
| Ramp Time | 1 ... 120 s |
| Initial Voltage During Start | 10 ... 99 % |
| Step Down Voltage Special Ramp | 100 ... 10 % |
| Current Limit Function | 1.5 ... 7.5 xle |
| Switch for Inside Delta Connection | Yes |
| Run Signal Relay | Yes |
| By-pass Signal Relay | Yes |
| Fault Signal Relay | Yes |
| Overload Signal Relay | Yes |
| Analog Outputs | 0…10 V, 0…20 mA, 4…20 mA |
| Signal Indication Ready to Start/Standby ON (LED) | Green |
| Signal Indication Running R (LED) | Green |
| Signal Indication Protection (LED) | Yellow |
| Signal Indication Fault (LED) | Red |
| Communication | Modbus-RTU; Modbus-TCP; Ethernet-IP; EtherCAT; DeviceNet; CANopen; Profibus; Profinet; BACnet-IP; BACnet-MSTP |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00 |
| Terminal Type | Main Circuit: Bars |
| Connecting Capacity Main Circuit | Hole Diameter 8.5 mm |
| Connecting Capacity Control Circuit | Rigid 1 x 2.5 mm² |
| Connecting Capacity Supply Circuit | Rigid 1 x 2.5 |
| Tightening Torque | Main Circuit 14 N·m |
| Product Main Type | PSTX142 |
| Function | Auto phase sequence detection; Automatic restart; Current limit; Current limit ramp; Dual current limit; Dynamic brake; Electricity metering; Electronic overload Time-to-cool; Emergency mode; Event log; Full voltage start; Jog with slow speed, forward and reverse; Keypad password; Kick start; Limp mode with two-phase motor control if one set of thyristors is shorted; Motor heating; Pre-start function; Pump cleaning; Real time clock; Sequence start; Soft start with torque control; Soft start with voltage ramp; Soft stop with torque control; Soft stop with voltage ramp; Stand still brake; Start reverse (external contactors); Thyristor runtime measurement; Torque limit; Voltage sags detection |
| Protection Function | Bypass open protection; Current imbalance protection; Current underload protection; Dual overload (separate overload for start and run); Earth fault protection / ground fault protection; Electronic overload protection, EOL; Extension IO failure protection; Fieldbus failure protection; HMI failure protection; Locked rotor protection; Max number of starts/hour; Over voltage protection; Phase reversal protection; Power factor underload protection; PT-100 connection; PTC connection; Too long current limit protection; Too long start time protection; Under voltage protection; User defined protection; Voltage imbalance protection |
| Warning Details | Current imbalance warning; Current underload warning; Electronic overload Time-to-trip; EOL warning; Faulty fan warning; Locked rotor warning; Motor runtime limit warning; Over voltage warning; Phase loss warning (for standby); Power factor underload warning; Short circuit warning (for Limp mode); THD(U) - Total Harmonic Distortion warning; Thyristor overload warning (SCR); Under voltage warning; Voltage imbalance warning |
| Horsepower Rating UL/CSA | (200 ... 208 V AC) Three Phase 40 Hp; (220 ... 240 V AC) Three Phase 50 Hp; (440 ... 480 V AC) Three Phase 100 Hp; (550 ... 600 V AC) Three Phase 125 Hp |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V |
| Tightening Torque UL/CSA | Main Circuit 123.9 |
| Ambient Air Temperature | Operation -25 ... +60 °C; Storage -40 ... +70 °C |
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| EcoSolutions Profile | 1SFC100125C0367 |
| End Of Life Disassembling Instructions | 1SFC132451M0201 |
| Environmental Product Declaration - EPD | 1SFC132445; 1SFC132436 |
| Extended Product Lifetime | Product Durability |
| Improved Energy Efficiency for Customers | Product Efficiency - Product considered more energy-efficient compared to similar product on market or older products from the same line |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 74.8 % |
| CQC Certificate | CN: CQC2014010304744407 / SE: CQC2014010304724379 |
| Declaration of Conformity - CCC | CN: 2020980304001092 / SE: 2020980304001485 |
| Declaration of Conformity - CE | 2CMT005209 |
| DNV Certificate | TAE000087N |
| EU Data Act Compliance Declaration | 1SFC132498M0201 |
| Object Classification Code | Q |
| ETIM 7 | EC000640 - Soft starter |
| eClass | V11.0 : 27370907 |
| UNSPSC | 39121521 |
| IDEA Granular Category Code (IGCC) | 4740 >> Soft starter |