| Manufacturer part number (MPN) | DS203NC C25 A30 |
| EAN / GTIN | 8012542768524 |
| Sales unit | pcs |
| Carbon Footprint (Full Lifecycle) | 10.992364 kg CO₂ eq |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 83.26 % |
| Sustainable Material Content in Packaging (wt. %) | Recycled Paper - 00 %; Recycled Cardboard - 92 %; Recycled Paper - 00 % |
| Extended Product Lifetime | Product Durability |
| End Of Life Disassembling Instructions | 9AKK108469A7475 |
| Environmental Product Declaration - EPD | 9AKK108469A9830 |
| Type of Residual Current | Type A |
| Rated Ultimate Short-Circuit Breaking Capacity (I cu ) | 10 kA |
| Power Supply Connection | Arbitrary |
| Energy Limiting Class | 3 |
| Electrical Endurance | 10000 cycle |
| Mechanical Endurance | 20000 cycle |
| Number of Protected Poles | 3 |
| Number of Poles | 3P+N |
| Operating Characteristic | Instantaneous |
| Position of Neutral Terminals | Right |
| Earthing Switch Type | Undelayed |
| Options Provided | None |
| Accessories Available | Yes |
| Connecting Capacity | Busbar 10 mm²; Rigid 25 ... 25 mm²; Flexible 25 ... 25 mm² |
| Rated Cross-Section | 1 - Solid-Core 25 … 25 mm²; 4 - Multi-Wired 1 … 25 mm² |
| Tripping Characteristic | C |
| Rated Operational Voltage | acc. to IEC 60898-1 415 V |
| Rated Insulation Voltage (U i ) | acc. to IEC/EN 60664-1 500 V |
| Rated Impulse Withstand Voltage (U imp ) | 4 kV |
| Input Voltage Type | AC |
| Rated Current (I n ) | 25 A |
| Rated Residual Current | 30 mA |
| Rated Short-Circuit Capacity | 6 kA |
| Rated Conditional Short-Circuit Current (I nc ) | 10 kA |
| Rated Frequency (f) | 50/60 Hz |
| Power Loss | Total 10.3 W |
| Overvoltage Category | III |
| Ambient Air Temperature | Operation -25 … 55 °C |
| Degree of Protection | IP2X |
| Pollution Degree | 2 |
| Environmental Information | refer to RoHS information |
| Width in Number of Modular Spacings | 4 |
| Product Net Width | 71 mm |
| Product Net Height | 85 mm |
| Product Net Depth / Length | 69 mm |
| Built-In Depth ( t 2 ) | 69 mm |
| Dimension Diagram | 9AKK106930A2210 |
| EPLAN Data | 9AAC181438_EPLAN |
| Building Information Modeling – BIM | 9AKK108471A7299 |
| CCC Certificate | 2021980307001650 |
| Declaration of Conformity - CE | 9AKK106713A5597 |
| Instructions and Manuals | 9AKK106713A8790 |
| Mounting Type | DIN-Rail |
| ETIM 9 | EC000905 - Earth leakage circuit breaker |
| UNSPSC | 39121601 |
| eClass | V11.0 : 27142207 |
| IDEA Granular Category Code (IGCC) | 4875 >> Residual current circuit breaker (RCCB) |
| Object Classification Code | F |
| Standards | IEC 61009-1; IEC 61009-2-1; EN 61009-1; EN 61009-2-1 |
| Rated voltage | 415 V |
| Rated insulation voltage Ui | 500 V |
| Rated impulse withstand voltage Uimp | 4 kV |
| Rated fault current | 0.03 A |
| Leakage current type | A |
| Rated short-circuit breaking capacity according to EN 60898 | 6 kA |
| Current limiting class | 3 |
| Rated short-circuit breaking capacity according to EN 61009 | 6 kA |
| Disconnection characteristic | Undelayed |
| Surge current capacity | 0.25 kA |
| Voltage type | AC |
| Frequency | 50/60 Hz |
| Release characteristic | C |
| Concurrently switching neutral conductor | Yes |
| With interlocking device | Yes |
| Ambient temperature during operating | -25–55 °C |
| Anti-nuisance tripping version | No |
| Connectable conductor cross section solid-core | 25 mm² |
| Connectable conductor cross section multi-wired | 25 mm² |
| Flush-mounted installation | No |
| Mounting method | DIN rail |
| Country of origin | Italy |