Residual Current Circuit Breaker F202 A S-100A/500MA (2CSF202201R4900)

ABB · Electrical Components · RCDs & RCBOs · Switzerland · abb.com
Part Number
2CSF202201R4900  ·  HS 8536.90
Residual Current Circuit Breaker F202 A S-100A/500MA (2CSF202201R4900)

ABB 2CSF202201R4900 — The RCCBs F200 series assures protection to people and installations against fault current to earth. A large offer for standard instantaneous and selective AC and A types is completed with some configurations for special applications.

Technical Specifications

Manufacturer part number (MPN)2CSF202201R4900
EAN / GTIN8012542916208
HS code8536.90
Sales unitpcs
Carbon Footprint (Full Lifecycle)8.966856 kg CO₂ eq
EcoSolutions Profile9AKK108469A3794
Recyclability Rate of the Product acc. to EN45555Design for Closing Resource Loops - Standard EN45555 - 82.05 %
ABB Site Meeting Group Waste To Landfill TargetNo non-hazardous waste is sent to a landfill; UL 2799 Zero Waste To Landfill Validation available
Sustainable Material Content in Packaging (wt. %)Recycled Paper - 0 %; Recycled Paper - 3.91 %; Recycled Cardboard - 29.08 %; Recycled Cardboard - 61.23 %; Recycled Cardboard - 2.66 %
Extended Product LifetimeProduct Durability
Offered with Takeback ServicesTake Back for Recycling
End Of Life Disassembling Instructions9AKK108470A1748
Environmental Product Declaration - EPD9AKK108469A9642
Type of Residual CurrentType A
Test Voltage (Out)110-254 V
Maximum Surge Current5 kA
Leakage Current TypeA
Power Supply ConnectionArbitrary
Electrical Endurance10000 cycle
Mechanical Endurance20000 cycle
Number of Poles2P
Number of Modular Spacings per DIN Rail2
Operating CharacteristicSelective
Tightening Torque2.8 N·m
Accessory TypeAuxiliary contact; Auxiliary/Signal contact; Shunt trip; Undervoltage release; Overvoltage release; Motor Operating Device; Autoreclosing Unit
Screw Terminal TypeCage Terminal
Options ProvidedNone
Accessories AvailableYes
Connecting CapacityBusbar 10 mm²; Rigid 35 ... 35 mm²; Flexible 35 ... 35 mm²
Rated Cross-Section4 - Multi-Wired 0...35 mm²; 1 - Solid-Core 35...35 mm²
Wire Stripping LengthTop 12.7 mm; Bottom 14.9 mm
Terminal TypeScrew Terminals
Rated Voltage (U r )230 V
Rated Operational Voltage230 V
Rated Insulation Voltage (U i )500 V
Rated Impulse Withstand Voltage (U imp )4 kV
Input Voltage TypeAC
Rated Current (I n )100 A
Rated Residual Current500 mA
Rated Conditional Short-Circuit Current (I nc )10 kA
Frequency ( f )50/60 Hz
Rated Frequency (f)50/60 Hz
Power Lossat Rated Operating Conditions per Pole 6.5 W; Total 13 W
RAL NumberRAL 7035 - Light Grey
Number of Modules2
Maximum Operating Voltage UL/CSA277 V AC
Ambient Air TemperatureOperation -25 ... 55 °C; Storage -40 ... 70 °C
Degree of ProtectionTerminals IP20; Housing IP40
Pollution Degree2
Resistance to Vibrations20 Cycles with Load 0.8 In: 1g or 0.1mm 5...150...5 Hz
Resistance to Shock acc. to IEC 60068-2-2725g 2 shocks 13 ms
Environmental InformationRefer to RoHS
Width in Number of Modular Spacings2
Product Net Width35 mm
Product Net Height85 mm
Product Net Depth / Length69 mm
Built-In Depth ( t 2 )69 mm
EPLAN Data9AAC202083_EPLAN
Declaration of Conformity - CE9AKK106713A5602
Instructions and Manuals9AKK107991A6127
Mounting TypeDIN-Rail
Mounting PositionAny
ETIM 9EC000003 - Residual current circuit breaker (RCCB)
UNSPSC39121601
eClassV11.0 : 27142201
IDEA Granular Category Code (IGCC)4875 >> Residual current circuit breaker (RCCB)
Object Classification CodeF
StandardsIEC/EN 61008; UL 1053

Properties

MOQ1

Cross-References