cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

ABB DDA803 RCD Block — 3-Pole, Type A, 63 A, 30 mA, Instantaneous, for S800 MCB (2CSB803101R1630)

ABB · Electrical Components · RCDs & RCBOs · Switzerland · abb.com
Part Number
2CSB803101R1630  ·  HS 8536.30
ABB DDA803 RCD Block — 3-Pole, Type A, 63 A, 30 mA, Instantaneous, for S800 MCB (2CSB803101R1630)

The ABB 2CSB803101R1630 is a DDA803 residual current device (RCD) block from the DDA800 range. It assembles on site onto an ABB S800 series miniature circuit breaker and adds residual-current protection to that breaker's overcurrent protection. Building a board this way means the earth-fault function can be added only to the ways that need it, instead of holding a separate RCBO in every rating. It is 3-pole, rated 63 A, with a rated residual current of 30 mA. Type A means it responds to sinusoidal AC residual currents and to pulsating DC residual currents, which is what circuits feeding electronic loads require. At 30 mA it is rated for protection of people against electric shock, which is the sensitivity required for socket outlets and other circuits where direct contact is foreseeable. It has an instantaneous tripping characteristic. Rated voltage 400 V AC; 415 V AC; 690 V AC. It fits S800P, S800S, S800N, S800C and S800B miniature circuit breakers. Supplied by cBallast on quote-to-invoice terms; lead time and freight are quoted per RFQ against the destination Incoterm.

Technical Specifications

Manufacturer part number (MPN)2CSB803101R1630
EAN / GTIN8012542922308
Sales unitpcs
Rated current63 A
Configuration OnlyNo
Country of OriginItaly
CriticalityNo
Lead Time48 day
NoteNo
Product Availability ClassStandard delivery time
Product Sales StatusActive
Storage Location4001
Technical Information10kA, 690VAC, A-Tyyppi
Type of Residual CurrentType A
Suitable ForS800P; S800S; S800N; S800C; S800B
Maximum Surge Current0.25 kA
Leakage Current TypeA
Number of Poles3P
Operating CharacteristicInstantaneous
Connecting CapacityRigid 6 ... 50 mm²; Flexible 6 ... 70 mm²
Short-Circuit Current Rating (SCCR)0.03 ... 0.03 A
Rated Voltage (U r )400 V AC; 415 V AC; 690 V AC
Rated Operational Voltage400/690 V
Rated Insulation Voltage (U i )acc. to IEC/EN 60664-1 690 V
Rated Impulse Withstand Voltage (U imp )6 kV
Rated Current (I n )63 A
Rated Residual Current30 mA
Rated Frequency (f)50 / 60 Hz
Power LossTotal 13.5 W
Ambient Temperature-25...60 °C
Ambient Air TemperatureOperation -25 ... 60 °C
Degree of ProtectionIP2X
Pollution Degree2
Environmental Informationdocument not needed
Width in Number of Modular Spacings6.5
Product Net Width117 mm
Product Net Height108.2 mm
Product Net Depth / Length82.3 mm
Declaration of Conformity - CE9AKK106713A5616
Instructions and Manuals2CSB427001D0003
ETIM 9EC002297 - Residual current circuit breaker (RCCB) module
UNSPSC39121601
eClassV11.0 : 27142210
IDEA Granular Category Code (IGCC)4875 >> Residual current circuit breaker (RCCB)
Object Classification CodeF
StandardsIEC EN 60947-2 Ann. B
Nominal voltage400–690 V
Nominal current63 A
Rated fault current adjustableNo
Rated fault current0.03 A
Delay adjustableNo
Surge current capacity0.25 kA
Frequency50/60 Hz
Rated insulation voltage Ui690 V
Rated impulse withstand voltage Uimp6 kV
Connectable conductor cross section solid-core6–50 mm²
Connectable conductor cross section multi-wired6–70 mm²
Anti-nuisance tripping versionNo
With interlocking deviceNo
Ambient temperature during operating-25–60 °C
Product familyABB DDA800 RCD block (System pro M compact)
Device typeAdd-on residual current device (RCD) block for MCB
ModelDDA803
Tripping characteristicInstantaneous
Protection purposeProtection of people against electric shock

Properties

MOQ1

Cross-References

Attached Documents