| Manufacturer part number (MPN) | 2CTB815710R5600 |
| EAN / GTIN | 3660308525215 |
| Sales unit | pcs |
| Carbon Footprint (Full Lifecycle) | 6.101598 kg CO₂ eq |
| EcoSolutions Profile | 9AKK108472A3406 |
| Type of Low Voltage Distribution System | TT; TN-S |
| Suitable For | To protect the systems against the transient overvoltage (lightning) |
| Nominal AC Voltage of the System (U o ) | 400 / 690 V |
| Maximum Continuous Operating Voltage (U c ) | (L-PE) - V; (L-L) - V; (L-N) - V; (N-PE) 440 V |
| Temporary Overvoltage Test Value (U T ) | 1200 V |
| Discharge Current | Nominal 50 kA; Maximum 100 kA |
| Impulse Current | I (imp, 10 / 350 µs, L-N) - kA; I (total, 10 / 350 µs) 50 kA |
| Lightning Impulse Current | 50 kA |
| Short Circuit Withstand Icc | 100 A |
| Arrester Class | I; II |
| Number of Protected Poles | 1 |
| Number of Poles | 1P |
| Version | Plug-in |
| Product Type | QS |
| Options Provided | Replacement Cartridge |
| Preventive Maintenance Feature | Yes |
| Status Indicator | No |
| Fuse Size | 1 modular spacing |
| Voltage Protection Level ( Up) | (L-N) - kV; (N-PE) 1.9 kV; (L-PE) - kV |
| Degree of Protection | IP20 |
| Maximum Operating Altitude Permissible | Without Derating 5000 |
| Width in Number of Modular Spacings | 1 |
| Product Net Width | 17.6 mm |
| Product Net Height | 57 mm |
| Product Net Depth / Length | 67 mm |
| CQC Certificate | 9AKK107680A1975 |
| Declaration of Conformity - CE | 9AKK108466A4617 |
| Instructions and Manuals | 2CTC431030M1701 |
| Mounting Type | DIN-Rail |
| ETIM 9 | EC001457 - Combined arrester for power supply systems |
| UNSPSC | 39121610 |
| eClass | V11.0 : 27130808 |
| Object Classification Code | 141BEC |
| Standards | IEC 61643-11 / EN 61643-11 |
| Mounting method | DIN rail (top hat rail) 35 mm |
| Construction size | 1 modular spacing |
| Exhausting | No |
| Remote signalling | No |
| Max. continuous voltage AC | 440 V |
| Nominal voltage AC | 400 V |
| Test class | Type 1 + 2 |
| Signalling at the device | None |
| Voltage protection level N-PE | 1.9 kV |
| Integrated backup fuse | No |
| System configuration DC | No |
| System configuration IT | No |
| System configuration TN | No |
| System configuration TN-C | No |
| System configuration TT | Yes |
| System configuration other | No |
| Voltage protection level L-PE | 1.9 kV |
| Voltage switching spark gap technology | No |
| Overcurrent protected voltage tapping | No |
| Country of origin | Bulgaria |