| Manufacturer part number (MPN) | 2CTB815710R1100 EAN / GTIN: 3660308524942 Sales unit: pcs Carbon Footprint (Full Lifecycle): 4.607503 kg CO₂ eq EcoSolutions Profile: 9AKK108472A3406 Environmental Product Declaration - EPD: 9AKK108472A1709 Type of Low Voltage Distribution System: TN-S Suitable For: To protect the systems against the transient overvoltage (lightning) Nominal AC Voltage of the System (U o ): 230 / 400 V Maximum Continuous Operating Voltage (U c ): (L-PE) 275 V; (L-L) 440 V; (L-N) 440 V; (N-PE) 275 V Temporary Overvoltage Test Value (U T ): 337 V Discharge Current: Nominal 20 kA; Maximum 80 kA; Total 320 kA Impulse Current: I (imp, 10 / 350 µs, L-N) 12.5 kA; I (total, 10 / 350 µs) 50 kA Lightning Impulse Current: 12.5 kA Short Circuit Withstand Icc: 100 kA Follow Current Extinction Capacity If (I fi): (L-N) - kA; (N-PE) - kA Short-Circuit Protective Devices: Curve B Breakers ≤ 125 A; Curve C Breakers ≤ 125 A; gL Type Fuses ≤ 160 A; gG Type Fuses ≤ 160 A Arrester Class: I; II Number of Protected Poles: 4 Number of Auxiliary Contacts NC: 1 Number of Auxiliary Contacts NO: 1 Number of Poles: 4P Position of Neutral Terminals: Right Version: Plug-in Product Type: QS Options Provided: Industry, commercial building Auxiliary Circuit Load: minimum 12Vdc - 10mA; Maximum 250Vac - 1A Preventive Maintenance Feature: Yes Status Indicator: Yes Fuse Size: 4 modular spacing Voltage Protection Level ( Up): (L-N) 2.8 kV; (N-PE) 1.4 kV; (L-PE) 1.4 kV Power Loss: Total 63 mW Degree of Protection: IP20 Maximum Operating Altitude Permissible: Without Derating 5000 Width in Number of Modular Spacings: 4 Product Net Width: 71.2 mm Product Net Height: 95.8 mm Product Net Depth / Length: 76.7 mm CQC Certificate: 9AKK107680A1975 Declaration: 2CTC432056G1701 Declaration of Conformity - CE: 9AKK108466A4617 Instructions and Manuals: 2CTC431030M1701 Mounting Type: DIN-Rail ETIM 9: EC001457 - Combined arrester for power supply systems UNSPSC: 39121610 eClass: V11.0 : 27130808 Object Classification Code: 141BCC Standards: IEC 61643-11 / EN 61643-11 System configuration DC: No System configuration IT: No System configuration TN: No System configuration TN-C: No System configuration TT: No System configuration other: No Nominal voltage AC: 230 V Nominal voltage DC: 350 V Max. continuous voltage AC: 275 V Max. continuous voltage DC: 350 V Voltage protection level L-N: 2.8 kV Voltage protection level N-PE: 1.4 kV Integrated backup fuse: No Mounting method: DIN rail (top hat rail) 35 mm Construction size: 4 modular spacing Max. conductor cross section solid (solid, stranded): 35 mm² Max. conductor cross section flexible (fine-strand): 25 mm² Signalling at the device: Optical Country of origin: Bulgaria |